'14 • SRK-T-155
CAUTION
Always use an earth leakage circuit breaker designed for inverter circuits to prevent a faulty operation.
Interconnecting and
grounding wires
(minimum)
Switch breaker
Over current protector
rated capacity
Power source
(minimum)
15A, 30mA,
0.1sec or less
30
A
16
A
2.0mm
2
1.5mm
2
X 4
Earth leakage breaker
Phase
Single-phase
•
The specifications shown in the above table are for units without heaters. For units with heaters, refer to the installation instructions or the construction instructions of the indoor unit.
•
Switchgear or Circuit breaker capacity which is calculated from MAX. over current should be chosen along the regulations in each country.
•
The cable specifications are based on the assumption that a metal or plastic conduit is used with no more than three cables contained in a conduit and a voltage drop is 2%. For an installation falling outside of these conditions, please follow the internal cabling regulations. Adapt it to the regulation in effect in each country.
Switchgear or Circuit Breaker
Power cable, indoor-outdoor connecting wires
•
Always perform grounding system installation work with the power cord unplugged.
•
Connect a pair bearing a common terminal number with an indoor-outdoor connecting wire.
•
In cabling, fasten cables securely with cable clamps so that no external force may work on terminal connections.
•
Grounding terminals are provided in the control box.
N
L
1
2/N
3
1
2/N
3
Safety breaker 16A
Earth leakage circuit breaker
htr
a
E
htr
a
E
Power supply
Indoor
unit
Outdoor
unit
When
wire
length
exceeds
30m,
use
2.5mm
2
wires.
Model SRC-ZM-S Model SRC-ZMX-S
N
L
D
1
D
2
D3
C
D
1
D2
D3
Safety breaker 16A
Earth leakage circuit breaker
Power supply
DRED*
Outdoor
unit
1
2/N
3
1
2/N
3
Indoor
unit
When
wire
length
exceeds
30m,
use
2.5mm
2
wires.
Model SRC-ZMA-S Model SRC-ZMXA-S
Model DXC-ZMA-S
C
Connecting
cable
between
outdoor
unit
and
DRED
shall
be
double
insulation
layer
,
polychloroprene
sheathed
(>50V)
with
size
4
x
(0.5mm
2
to
2.0mm
2
)
cable
or
flexible
cord,
where
the
maximum
allowable
length
is
30m.
*Demand response enabling devices
Power cable, indoor - outdoor connecting wire circuit diagram
Model SRC20
~
35ZM-S
Model SRC20
~
35ZMX-S
Model SRC20
~
35ZMA-S
Model SRC20
~
35ZMXA-S
Model DXC09,12ZMA-S
Model SRC50ZM-S
Model SRC50ZMA-S Model DXC18ZMA-S
Power cable
Indoor - Outdoor connecting wire
Indoor - Outdoor connecting wire
DRED cable (Demand response enabling devices)
Power cable
Indoor - Outdoor connecting wire
Indoor - Outdoor connecting wire
Power cable
DRED cable (Demand response enabling devices)
Power cable
•Earth wire shall be Yellow/Green (Y/G) in color and longer than other AC wires for safety reason.
•Earth wire shall be Yellow/Green (Y/G) in color and longer than other AC wires for safety reason.
Cable name plate
•
It holds cables in place and protect the terminal connection from external force.
•
This clamp is for the cable in the outside diameter 9
~
15mm.
Please adjust it when not suitable.
•
Please be sure to carry out D-type (type III) grounding work.
•
It has stuck on the lid of a control box.
Grounding terminal
Power supply terminal block
Cable clamp
Summary of Contents for SRC20ZMX-SA
Page 2: ......
Page 3: ... 14 SRK T 155 TECHNICAL MANUAL ...
Page 14: ... 12 14 SRK T 155 3 Remote control Unit mm 60 26 167 a Wireless remote control ...
Page 99: ... 97 14 SRK T 155 WARING CAUTION 3 Super link E board SC ADNA E F ...
Page 100: ... 98 14 SRK T 155 ...
Page 105: ... 103 14 SRK T 155 MEMO ...
Page 111: ... 109 14 SRK T 155 MEMO ...
Page 117: ... 115 14 SRK T 155 MEMO ...
Page 123: ... 121 14 SRK T 155 MEMO ...
Page 129: ... 127 14 SRK T 155 MEMO ...
Page 132: ... 130 14 SRK T 155 CRBE0276 6 13 11 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY ...
Page 136: ... 134 14 SRK T 155 CRBE0276 6 13 11 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY ...
Page 140: ... 138 14 SRK T 155 CRBE0276 6 13 11 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY ...
Page 144: ... 142 14 SRK T 155 CRBE0315 9 13 15 16 14 17 7 6 4 1 8 3 11 5 18 10 10 10 2 12 PANEL FAN ASSY ...
Page 148: ... 146 14 SRK T 155 CRBE0315 9 13 15 16 14 17 7 6 4 1 8 3 11 5 18 10 10 10 2 12 PANEL FAN ASSY ...