59
-
'14 • SRK-T-155
(f)
Heating high pressure control
(i)
Purpose:
Prevents anomalous high pressure operation during heating.
(ii)
Detector:
Indoor heat exchanger sensor (Th2)
(iii)
Detail of operation:
A
B
C
D
Indoor heat exchanger temperature(°C)
4rps
(1)
8rps
(2)
8rps
(2)
4rps
(1)
0rps
After lapse of 20 (10) sec. or over
(3)
After lapse of 20 (10) sec. or over
(3)
After lapse of 20 (10) sec. or over
(3)
lower limit
speed 30(model SRK50, 60:35)rps
(Example) Fuzzy
Notes (1) When the indoor heat exchanger temperature is in the range of B~C ºC, the speed is reduced by 4 rps at each 20 (10) seconds.
(2) When the indoor heat exchanger temperature is in the range of C~D ºC, the speed is reduced by 8 rps at each 20 (10) seconds. When the tempera-
ture is D ºC or higher continues for 1 minute, the compressor is stopped.
(3) When the indoor heat exchanger temperature is in the range of A~B ºC, if the compressor command speed is been maintained and the operation has
continued for more than 20 (10) seconds at the same speed, it returns to the normal heating operation.
(4) Indoor blower retains the fan tap when it enters in the high pressure control. Outdoor blower is operated in accordance with the speed.
(5) Value in ( ) are for the model SRK50, 60.
¡
Temperature list
A
B
C
D
RPSmin < 50
48
53
55
58
50 <= RPSmin < 95
48.5
56
58
61
95 <= RPSmin < 97
48.5
56 ~ 55.5
58
61
97 <= RPSmin < 104
48.5
55.5 ~ 51.5
58 ~ 53.5
61
104 <= RPSmin < 115
48.5 ~ 42.1
51.5 ~ 44
53.5 ~ 47.3
61
115 <= RPSmin
42.1
44
47.3
61
Note (1) RPSmin: The lower one between the outdoor speed and the compressor command speed.
Models SRK20~35
A
B
C
D
RPSmin < 50
45
52
54.5
61
50 <= RPSmin < 115
45
52
57
61~51.5
115 <= RPSmin < 120
45~43
52~50
57
51.5
120 <= RPSmin
43
50
55
51.5
Models SRK50, 60
Unit : ºC
Note (1) RPSmin: The lower one between the outdoor speed and the compressor command speed
Unit : ºC
'09•SRK-DB-087D
(g) Heating overload protective control
(i)
Indoor unit side
1) Operating conditions :
2) Detail of operation :
3) Reset conditions :
(ii)
Outdoor unit side
1) Operating conditions :
2) Detail of operation
3) Reset conditions:
(i)
Operating conditions:
(ii)
Detail of operation:
(h) Heating low outdoor temperature protective control
(iii) Reset conditions:
-10
-8
-2
2
Lower limit 45 rps
Lower limit 40 rps
Normal operation
Outdoor air temperature(°C)
10
11
19
20
Normal operation
Protective control ON1
Protective control ON2
Outdoor air temperature(°C)
21
22
Normal operation
Protective
control
Outdoor air temperature(°C)
• Model SRK50
• Model 50
• Models SRK20 ~ 35
• Models SRK20 ~ 35
(i)
ࠉ
Operating conditions:
When the outdoor air temperature (TH2) is lower than 4ºC or 13ºC or higher continues for 30
seconds while the compressor command speed is other than 0 rps.
(ii)
ࠉ
Detail of operation:
The lower limit compressor command speed is change as shown in the figure belo.
Lower limit 29 rps
Normal operation
4
6
Outdoor air temperature(°C)
Model SRK50
A
B
C
D
RPSmin < 40
40 <= RPSmin < 80
80 <= RPSmin < 90
90 <= RPSmin < 102
102 <= RPSmin
49
53
41
53 ~ 47
47 ~ 41
53
57
45
57 ~ 51
51 ~ 45
55
59
47
59 ~ 53
53 ~ 47
58
62
51
58
51
When the outdoor air temperature (TH2) is 22ºC or higher continues for 30 seconds while
the compressor command speed other than 0 rps.
a)
b)
c)
d)
Taking the upper limit of compressor command speed range at 60 rps, if the output speed obtained with the fuzzy
calculation exceeds the upper limit, the upper limit value is maintained.
The lower limit of compressor command speed is set to 40 rps and even if the calculated result becomes lower than
that after fuzzy calculation, the speed is kept to 40 rps. However, when the
thermo OFF, the speed is reduced to 0 prs.
rps.
1) Operating conditions :
2) Detail of operation
When the outdoor air temperature (TH2) is 11ºC or higher continues for 30 seconds while
the compressor command speed other than 0 rps.
a)
b)
c)
d)
Taking the upper limit of compressor command speed range at 78 rps, if the output speed obtained with the fuzzy
calculation exceeds the upper limit, the upper limit value is maintained.
The lower limit of compressor command speed is set to 30 rps and even if the calculated result becomes lower than
that after fuzzy calculation, the speed is kept to 30 rps. However, when the
thermo becomes OFF, the speed is
reduced to 0 prs.
rps.
.
3) Reset conditions:
.
1)
2)
30
Protective
control
ON1
ON2
Item
Compressor command speed
Low limit
30 rps
30 rps
Upper limit
78 rps
51 rps
It depends on compressor command speed
Outdoor fan speed
2nd
10
Summary of Contents for SRC20ZMX-SA
Page 2: ......
Page 3: ... 14 SRK T 155 TECHNICAL MANUAL ...
Page 14: ... 12 14 SRK T 155 3 Remote control Unit mm 60 26 167 a Wireless remote control ...
Page 99: ... 97 14 SRK T 155 WARING CAUTION 3 Super link E board SC ADNA E F ...
Page 100: ... 98 14 SRK T 155 ...
Page 105: ... 103 14 SRK T 155 MEMO ...
Page 111: ... 109 14 SRK T 155 MEMO ...
Page 117: ... 115 14 SRK T 155 MEMO ...
Page 123: ... 121 14 SRK T 155 MEMO ...
Page 129: ... 127 14 SRK T 155 MEMO ...
Page 132: ... 130 14 SRK T 155 CRBE0276 6 13 11 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY ...
Page 136: ... 134 14 SRK T 155 CRBE0276 6 13 11 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY ...
Page 140: ... 138 14 SRK T 155 CRBE0276 6 13 11 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY ...
Page 144: ... 142 14 SRK T 155 CRBE0315 9 13 15 16 14 17 7 6 4 1 8 3 11 5 18 10 10 10 2 12 PANEL FAN ASSY ...
Page 148: ... 146 14 SRK T 155 CRBE0315 9 13 15 16 14 17 7 6 4 1 8 3 11 5 18 10 10 10 2 12 PANEL FAN ASSY ...