'14 • SRK-T-155
Model
Item
SRK35ZMXA-S
Indoor unit
SRK35ZMXA-S
Outdoor unit
SRC35ZMXA-S
Power source
1 Phase, 220 - 240V, 50Hz
Operation
data
Nominal cooling capacity (range)
kW
3.5 ( 0.9 (Min.) - 4.1 (Max.))
Nominal heating capacity (range)
kW
4.3 ( 0.9 (Min.) - 5.1 (Max.))
Power
consumption
Cooling
kW
0.845 ( 0.19 - 1.01 )
Heating
0.960 ( 0.23 - 1.35 )
Max power consumption
1.65
Running
current
Cooling
A
4.0 / 3.8 / 3.6 (220/ 230/ 240 V)
Heating
4.6 / 4.4 / 4.2 (220/ 230/ 240 V)
Inrush current, max current
4.6 / 4.4 / 4.2 (220/ 230/ 240 V) Max. 8
Power factor
Cooling
%
97
Heating
95
EER
Cooling
4.14
COP
Heating
4.48
Sound power level
Cooling
dB(A)
58
63
Heating
59
62
Sound pressure level
Cooling
Hi: 43 Me: 33 Lo: 25 ULo: 22
50
Heating
Hi: 42 Me: 35 Lo: 27 ULo: 22
50
Silent mode sound pressure level
—
Cooling:45 / Heating:43
Exterior dimensions (Height x Width x Depth)
mm
309 x 890 x 220
595 x 780(+62) x 290
Exterior appearance
( Munsell color )
Fine snow
( 8.0Y 9.3/0.1 ) near equivalent
Stucco white
( 4.2Y 7.5/1.1 ) near equivalent
Net weight
kg
13.5
35
Compressor type & Q'ty
—
RM-B5077MDE1( Rotary type ) x 1
Compressor motor (Starting method)
kW
—
0.90 ( Inverter driven )
Refrigerant oil (Amount, type)
—
0.35 (DIAMOND FREEZE MA68)
Refrigerant (Type, amount, pre-charge length)
kg
R410A 1.2 in outdoor unit (incl. the amount for the piping of 15m )
Heat exchanger
Louver fins & inner grooved tubing
M fins & inner grooved tubing
Refrigerant control
Capillary tubes + Electronic expansion valve
Fan type & Q'ty
Tangential fan x 1
Propeller fan x 1
Fan motor (Starting method)
W
30 x1 (Direct drive)
24 x1 (Direct drive)
Air flow
Cooling
m
3
/min
Hi: 13.5 Me: 9.5 Lo: 6.5 ULo: 5.0
32.5
Heating
Hi: 14.0 Me: 11.0 Lo: 8.0 ULo: 6.5
29.5
Available external static pressure
Pa
0
0
Outside air intake
Not possible
—
Air filter, Quality / Quantity
Polypropylene net ( washable ) x 2
—
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber sleeve (for fan motor & compressor)
Electric heater
—
—
Operation
control
Remote control
Wireless remote control
Room temperature control
Microcomputer thermostat
Operation display
RUN: Green, TIMER: Yellow, HI POWER: Green, 3D AUTO: Green, ECONO: Blue
Safety equipments
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Heating overload protection (High pressure control), Cooling overload protection
Installation
data
Refrigerant piping size (O.D)
mm
Liquid line :
φ
6.35 (1/4") Gas line :
φ
9.52 (3/8")
Connecting method
Flare connection
Flare connection
Attached length of piping
m
Liquid line : 0.55 / Gas line : 0.49
—
Insulation for piping
Necessary (Both sides), independent
Refrigerant line (one way) length
m
Max. 15
Vertical height diff. between O.U. and I.U.
m
Max. 10 (Outdoor unit is higher) / Max. 10 (Outdoor unit is lower)
Drain hose
Hose connectable ( VP 16 )
Holes
φ
20 x 2 pcs
Drain pump, max lift height
mm
—
—
Recommended breaker size
A
16
L.R.A. (Locked rotor ampere)
A
4.6 / 4.4 / 4.2 (220/ 230/ 240 V)
Interconnecting wires
Size x Core number
1.5mm
2
x 4 cores (Including earth cable) / Terminal block (Screw fixing type)
IP number
IPX0
IPX4
Standard accessories
Mounting kit, Clean filter (Allergen clear filter x 1, Photocatalytic washable deodorizing filter x 1)
Option parts
Interface kit (SC-BIKN-E)
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO5151-T1
Heating
20˚C
—
7˚C
6˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
(5) This air-conditioner is compliant with DRED (AS/NZS 4755.3.1), and can operate with DRM1, 2 or 3, and is equipped with a terminal
block for DRED.
The pipe length is 7.5m.
C
RWA000Z252
Summary of Contents for SRC20ZMX-SA
Page 2: ......
Page 3: ... 14 SRK T 155 TECHNICAL MANUAL ...
Page 14: ... 12 14 SRK T 155 3 Remote control Unit mm 60 26 167 a Wireless remote control ...
Page 99: ... 97 14 SRK T 155 WARING CAUTION 3 Super link E board SC ADNA E F ...
Page 100: ... 98 14 SRK T 155 ...
Page 105: ... 103 14 SRK T 155 MEMO ...
Page 111: ... 109 14 SRK T 155 MEMO ...
Page 117: ... 115 14 SRK T 155 MEMO ...
Page 123: ... 121 14 SRK T 155 MEMO ...
Page 129: ... 127 14 SRK T 155 MEMO ...
Page 132: ... 130 14 SRK T 155 CRBE0276 6 13 11 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY ...
Page 136: ... 134 14 SRK T 155 CRBE0276 6 13 11 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY ...
Page 140: ... 138 14 SRK T 155 CRBE0276 6 13 11 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY ...
Page 144: ... 142 14 SRK T 155 CRBE0315 9 13 15 16 14 17 7 6 4 1 8 3 11 5 18 10 10 10 2 12 PANEL FAN ASSY ...
Page 148: ... 146 14 SRK T 155 CRBE0315 9 13 15 16 14 17 7 6 4 1 8 3 11 5 18 10 10 10 2 12 PANEL FAN ASSY ...