background image

'20 • SRF-DB-310

-

 43 

-

 WARNING

RSA012A061B

WALL TYPE AIR-CONDITIONER

R32 REFRIGERANT USED

is leaked, together with an external ignition source, there is a 

possibility of ignition.

There is information included in the user’s manual and/or 

installation manual.

The user’s manual should be read carefully.

A service personnel should be handing this equipment with 

reference to the installation manual.

•  This safety precaution sheet is for R32 refrigerant. If you want to know the type of refrigerant in the unit, check the label attached to the outdoor unit.

•  The precautionary items mentioned below are distinguished into two levels, 

 WARNING

 and 

 CAUTION

.

 WARNING

 : Wrong installation would cause serious consequences such as injuries or death.

 CAUTION

 : Wrong installation might cause serious consequences depending on circumstances.

 CAUTION

1.  General

•  That the installation of pipe-work shall be kept to a 

minimum.

•  That pipe-work shall be protected from physical 

damage.

•  That compliance with national gas regulations shall 

be observed.

•  That mechanical connections shall be accessible 

for maintenance purposes.

•  Keep any required ventilation openings clear of 

obstruction.

•  Servicing shall be performed only as recommended 

by the manufacturer.

2.  Unventilated areas

•  The appliance shall be stored in a well-ventilated 

area where the room size corresponds to the room 

3. 

•  The staff in servicing operations must hold the 

4.  Information on servicing

4.1  Checks to the area

•  Prior to beginning work on systems containing 

necessary to ensure that the risk of ignition is 

minimised.

•  For repair to the refrigerating system, 4.3 to 4.7 

shall be completed prior to conducting work on the 

system.

4.2  Work procedure

•  Work shall be undertaken under a controlled 

gas or vapour being present while the work is being 

performed.

4.3  General work area

•  All maintenance staff and others working in the 

local area shall be instructed on the nature of work 

being carried out.

• 

•  The area around the workspace shall be sectioned off.

•  Ensure that the conditions within the area have 

4.4  Checking for presence of refrigerant

•  The area shall be checked with an appropriate 

refrigerant detector prior to and during work, to 

ensure the technician is aware of potentially toxic or 

•  Ensure that the leak detection equipment being 

used is suitable for use with all applicable 

refrigerants, i.e.  

non-sparking, adequately sealed or intrinsically 

safe.

4.5 

•  If any hot work is to be conducted on the 

refrigeration equipment or any associated parts, 

available to hand. Have a dry powder or CO

2

extinguisher adjacent to the charging area.

4.6  No ignition sources

•  No person carrying out work in relation to a 

refrigeration system which involves exposing any 

pipe work shall use any sources of ignition in such 

explosion.

•  All possible ignition sources, including cigarette 

the site of installation, repairing, removing and 

disposal, during which refrigerant can possibly be 

released to the surrounding space.

•  Prior to work taking place, the area around the 

equipment is to be surveyed to make sure that 

•  “No Smoking” signs shall be displayed.
4.7  Ventilated area

•  Ensure that the area is in the open or that it is 

adequately ventilated before breaking into the 

system or conducting any hot work.

•  A degree of ventilation shall continue during the 

period that the work is carried out.

•  The ventilation should safely disperse any released 

refrigerant and preferably expel it externally into the 

atmosphere.

4.8  Checks to the refrigeration equipment

•  Where electrical components are being changed, 

•  At all times the manufacturer’s maintenance and 

service guidelines shall be followed.

•  If in doubt consult the manufacturer’s technical 

department for assistance.

•  The following checks shall be applied to 

– the charge size is in accordance with the room 

size within which the refrigerant containing parts 

are installed;

–  the ventilation machinery and outlets are 

operating adequately and are not obstructed;

–  if an indirect refrigerating circuit is being used, 

the secondary circuit shall be checked for the 

presence of refrigerant;

–  marking to the equipment continues to be visible 

and legible. Markings and signs that are illegible 

shall be corrected;

–  refrigeration pipe or components are installed in 

a position where they are unlikely to be exposed 

to any substance which may corrode refrigerant 

containing components, unless the components 

are constructed of materials which are inherently 

resistant to being corroded or are suitably 

protected against being so corroded.

4.9  Checks to electrical devices

•  Repair and maintenance to electrical components 

shall include initial safety checks and component 

inspection procedures.

•  If a fault exists that could compromise safety, then 

no electrical supply shall be connected to the circuit 

until it is satisfactorily dealt with.

•  If the fault cannot be corrected immediately but it 

is necessary to continue operation, an adequate 

temporary solution shall be used.

•  This shall be reported to the owner of the 

equipment so all parties are advised.

•  Initial safety checks shall include:

–  that capacitors are discharged: this shall be done 

in a safe manner to avoid possibility of sparking;

–  that no live electrical components and wiring are 

exposed while charging, recovering or purging 

the system;

–  that there is continuity of earth bonding.

5.  Repairs to sealed components

•  During repairs to sealed components, all electrical 

supplies shall be disconnected from the equipment 

being worked upon prior to any removal of sealed 

covers, etc.

•  If it is absolutely necessary to have an electrical 

supply to equipment during servicing, then a 

permanently operating form of leak detection shall 

be located at the most critical point to warn of a 

potentially hazardous situation.

•  Particular attention shall be paid to the following to 

ensure that by working on electrical components, 

the casing is not altered in such a way that the level 

of protection is affected. 

This shall include damage to cables, excessive 

number of connections, terminals not made to 

•  Ensure that the apparatus is mounted securely.

•  Ensure that seals or sealing materials have not 

degraded to the point that they no longer serve the 

atmospheres.

•  Replacement parts shall be in accordance with the 

NOTE

The use of silicon sealant can inhibit the effectiveness 

of some types of leak detection equipment.

Intrinsically safe components do not have to be 

isolated prior to working on them.

•  Strict compliance of the domestic laws must be 

observed when disposing the appliance.

•  Do not use means to accelerate the defrosting 

process or to clean, other than those recommended 

by the manufacturer.

•  The appliance shall be stored in a room without 

continuously operating ignition sources (for example: 

operating electric heater. 

•  Do not pierce or burn.

•  Be aware that refrigerants may not contain an 

odour.

•  The indoor unit shall be stored in a room that has a 

minimum area of 4.0 m

2

.

D

 CAUTION

6.  Repair to intrinsically safe components

•  Do not apply any permanent inductive or 

capacitance loads to the circuit without ensuring 
that this will not exceed the permissible voltage and 
current permitted for the equipment in use.

•  Intrinsically safe components are the only types that 

can be worked on while live in the presence of a 

•  The test apparatus shall be at the correct rating.
• 

the manufacturer.

•  Other parts may result in the ignition of refrigerant 

in the atmosphere from a leak.

7.  Cabling

•  Check that cabling will not be subject to wear, 

corrosion, excessive pressure, vibration, sharp 
edges or any other adverse environmental effects. 
The check shall also take into account the effects 
of aging or continual vibration from sources such as 
compressors or fans.

8. 

•  Under no circumstances shall potential sources of 

ignition be used in the searching for or detection of 
refrigerant leaks.

•  A halide torch (or any other detector using a naked 

9.  Leak detection methods

•  Electronic leak detectors may be used to detect 

refrigerants, the sensitivity may not be adequate, or 
may need re-calibration. (Detection equipment shall 
be calibrated in a refrigerant-free area.)

•  Ensure that the detector is not a potential source of 

ignition and is suitable for the refrigerant used.

•  Leak detection equipment shall be set at a 

percentage of the LFL of the refrigerant and shall 
be calibrated to the refrigerant employed, and the 
appropriate percentage of gas (25 % maximum) is 

• 

refrigerants but the use of detergents containing 
chlorine shall be avoided as the chlorine may 
react with the refrigerant and corrode the copper 
pipe-work.

• 

removed/extinguished.

•  If a leakage of refrigerant is found which requires 

brazing, all of the refrigerant shall be recovered 
from the system, or isolated (by means of shut off 
valves) in a part of the system remote from the 
leak.

• 

oxygen free nitrogen (OFN) shall then be purged 
through the system both before and during the 
brazing process.

10. Removal and evacuation

•  When breaking into the refrigerant circuit to make 

repairs – or for any other purpose – conventional 

refrigerants it is important that best practice is 

•  The following procedure shall be adhered to:

– remove refrigerant;
– purge the circuit with inert gas;
– evacuate;
– purge again with inert gas;
– open the circuit by cutting or brazing.

•  The refrigerant charge shall be recovered into the 

correct recovery cylinders.

• 

the unit safe. 
This process may need to be repeated several 
times.

•  Compressed air or oxygen shall not be used for 

purging refrigerant systems.

• 

the working pressure is achieved, then venting to 

 

This process shall be repeated until no refrigerant 
is within the system.

• 

shall be vented down to atmospheric pressure to 
enable work to take place. 
This operation is absolutely vital if brazing 
operations on the pipe-work are to take place.

•  Ensure that the outlet for the vacuum pump is not 

close to any ignition sources and that ventilation is 
available.

11. Charging procedures

•  In addition to conventional charging procedures, the 

following requirements shall be followed.
– Ensure that contamination of different refrigerants 

does not occur when using charging equipment. 
Hoses or lines shall be as short as possible to 
minimise the amount of refrigerant contained in 
them.

– Cylinders shall be kept upright.
– Ensure that the refrigeration system is earthed 

prior to charging the system with refrigerant.

– Label the system when charging is complete (if 

not already).

refrigeration system.

•  Prior to recharging the system, it shall be pressure-

tested with the appropriate purging gas.

•  The system shall be leak-tested on completion of 

charging but prior to commissioning.

•  A follow up leak test shall be carried out prior to 

leaving the site.

12. Decommissioning

•  Before carrying out this procedure, it is essential 

that the technician is completely familiar with the 
equipment and all its detail. 

•  It is recommended good practice that all 

refrigerants are recovered safely. 

•  Prior to the task being carried out, an oil and 

refrigerant sample shall be taken in case analysis is 
required prior to re-use of reclaimed refrigerant.

•  It is essential that electrical power is available 

before the task is commenced.

a) Become familiar with the equipment and its 

operation.

b) Isolate system electrically.
c) Before attempting the procedure ensure that:

– mechanical handling equipment is available, if 

required, for handling refrigerant cylinders;

– all personal protective equipment is available and 

being used correctly;

– the recovery process is supervised at all times by 

a competent person;

– recovery equipment and cylinders conform to the 

appropriate standards.

d) Pump down refrigerant system, if possible.
e)  If a vacuum is not possible, make a manifold so 

that refrigerant can be removed from various parts 
of the system.

f)   Make sure that cylinder is situated on the scales 

before recovery takes place.

g)  Start the recovery machine and operate in 

accordance with manufacturer’s instructions.

h)  

volume liquid charge).

i)   Do not exceed the maximum working pressure of 

the cylinder, even temporarily.

j)   

and the process completed, make sure that the 
cylinders and the equipment are removed from site 
promptly and all isolation valves on the equipment 
are closed off.

k) Recovered refrigerant shall not be charged into 

another refrigeration system unless it has been 
cleaned and checked.

13. Labelling

•  Equipment shall be labelled stating that it has been 

de-commissioned and emptied of refrigerant. The 
label shall be dated and signed.

• 

ensure that there are labels on the equipment 

refrigerant.

14. Recovery

•  When removing refrigerant from a system, either for 

servicing or decommissioning, it is recommended 
good practice that all refrigerants are removed 
safely.

•  When transferring refrigerant into cylinders, ensure 

that only appropriate refrigerant recovery cylinders 
are employed.

•  Ensure that the correct number of cylinders for 

holding the total system charge are available.

•  All cylinders to be used are designated for 

the recovered refrigerant and labelled for that 
refrigerant (i.e. special cylinders for the recovery of 
refrigerant).

•  Cylinders shall be complete with pressure relief 

valve and associated shut-off valves in good 
working order.

•  Empty recovery cylinders are evacuated and, if 

possible, cooled before recovery occurs.

•  The recovery equipment shall be in good working 

order with a set of instructions concerning the 
equipment that is at hand and shall be suitable 
for the recovery of all appropriate refrigerants 

•  In addition, a set of calibrated weighing scales shall 

be available and in good working order.

•  Hoses shall be complete with leak-free disconnect 

couplings and in good condition.

•  Before using the recovery machine, check that it 

is in satisfactory working order, has been properly 
maintained and that any associated electrical 
components are sealed to prevent ignition in the 
event of a refrigerant release. 
Consult manufacturer if in doubt.

•  The recovered refrigerant shall be returned to the 

refrigerant supplier in the correct recovery cylinder, 
and the relevant Waste Transfer Note arranged. 
Do not mix refrigerants in recovery units and 
especially not in cylinders.

•  If compressors or compressor oils are to be 

removed, ensure that they have been evacuated to 

refrigerant does not remain within the lubricant.

•  The evacuation process shall be carried out prior to 

returning the compressor to the suppliers.

•  Only electric heating to the compressor body shall 

be employed to accelerate this process.

•  When oil is drained from a system, it shall be 

carried out safely.

15. Other safety precautions

•  A brazed, welded, or mechanical connection shall 

be made before opening the valves to permit 

parts.

•  Flammable refrigerant used, refrigerant tubing 

protected or enclosed to avoid mechanical damage 
(IEC/EN 60335-2-40/A1).

•  Tubing protected to extent that it will not be handled 

or used for carrying during moving of product (IEC/
EN 60335-2-40/A1).

•  Flammable refrigerant used, low temperature solder 

alloys, such as lead/tin alloys, not acceptable for 
pipe connections (IEC/EN 60335-2-40/A1).

• 

outdoor.

RSA012A061B

Summary of Contents for SRC20ZS-W

Page 1: ...f the power source in the event of installation mainte nance or service If the power source is not switched off there is a risk of electric shock unit failure or personal injury Be sure to tighten the cables securely in terminal block and relieve the cables properly to prevent overloading the terminal blocks Loose connections or cable mountings can cause anomalous heat production or fire Do not pr...

Page 2: ... or snow accumulation the fol lowing measures are required 1 Location of strong wind Place the unit with its outlet side facing the wall Place the unit such that the direction of air from the outlet gets perpendicular to the wind direction Over 500mm Wind direction Wind direction 2 Location of snow accumulation Install the unit on the base so that the bottom is higher than snow cover surface Insta...

Page 3: ...charge can be calculated using the formula given below Additional refrigerant charge g Connecting pipe length m Factory charged length A m x 20 g m Model SRK SRR SRF35 FDTC Model SRF25 A Factory charged length m 15 10 NOTE If additional refrigerant charge calculation result is negative there is no need to remove the refrigerant If refrigerant recharge is required for the unit with connecting pipe ...

Page 4: ... may work on terminal connec tions Moreover make sure that cables do not touch the piping etc When cables are connected make sure that all electrical components within the electrical component box are free of loose connector coupling or terminal connection Circuit diagram N L 1 2 N 3 1 2 N 3 Circuit breaker Earth leakage breaker Earth Power source Indoor unit Outdoor unit Connecting cable Power so...

Page 5: ... power source is not switched off there is a risk of electric shock unit failure or personal injury a c e h t e v e i l e r d n a k c o l b l a n i m r e t n i y l e r u c e s s e l b a c e h t n e t h g i t o t e r u s e B bles properly to prevent overloading the terminal blocks Loose connections or cable mountings can cause anomalous heat production or fire h t i w t e k c o s e h t e r a h s r o...

Page 6: ...d out 1 Install drain elbow and drain grommet l a i r e t a m g n i k l u a c e t a u q e d a r o y t t u p h t i w t e m m o r g n i a r d d n a w o b l e n i a r d e h t d n u o r a l a e S 2 SRC20 25 35 40 50 60ZSX W Do not put a grommet on this hole This is a supplementary drain hole to discharge drain water when a large amount of it is gathered CAUTION Do not use drain elbow and drain grommet...

Page 7: ...ressure gauge Pressure gauge Gauge manifold Handle Hi Vacuum pump CAUTION To prevent vacuum pump oil from entering into the refrigerant system use a counterflow prevention adapter 5 Additional refrigerant charge Additional refrigerant charge is required only when connecting pipe length exceeds 15 m 5 1 Calculating additional refrigerant charge Additional refrigerant charge can be calculated using t...

Page 8: ...embly should be anchored ev ery 1 5m or less to isolate the vibration 3 Install the service cover securely Water may enter the unit if service cover is not installed properly resulting in unit malfunction and failure Pipe assembly Screw Clamp CAUTION Improper insulation can cause condensate water formation during cooling operation Condensate can leak or drip causing damage to household property Po...

Page 9: ...oor unit shall be stored in a room that has a minimum area of 4 0 m2 D WARNING RSA012A061B WALL TYPE AIR CONDITIONER R32 REFRIGERANT USED is leaked together with an external ignition source there is a possibility of ignition There is information included in the user s manual and or installation manual The user s manual should be read carefully A service personnel should be handing this equipment w...

Page 10: ...ts are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essential that electrical power is available before the task is commenced a Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that mechanical han...

Reviews: