background image

6. PUMP DOWN

(1) Connect charge hose of gauge manifold to service port of outdoor unit.

(2) Close the liquid service valve with hexagonal wrench key.

(3) Fully open the gas service valve with hexagonal wrench key.

(4) Carry out forced cooling operation (For forced cooling operation procedure, refer to indoor unit installation 

manual).

(5) When the low pressure gauge becomes 0.01 MPa, close the gas service valve and stop forced cooling 

operation.

Service port

Gauge manifold

Charge hose

 

7. ELECTRICAL WIRING WORK 

 WARNING

• Make sure that all the electrical work is carried out in accordance with the national or regional electrical 

standards.

• Make sure that the earth leakage breaker and circuit breaker of appropriate capacities are installed 

  (Refer to the table given below).

• Do not turn on the power until the electrical work is completed.

• Do not use a condensive capacitor for power factor improvement under any circumstances. 

  (It does not improve power factor. Moreover, it can cause an abnormal overheat accident).

Breaker specifications

Model

Phase

Earth leakage breaker

Circuit breaker

SRC20/25/35

Single phase

Leakage current: 30 mA, 

0.1sec or less

Over current: 16 A

SRC50

Over current: 20 A

Main fuse specification

Model

Specification

Parts No.

Code on LABEL,WIRING

SRC20/25/35

250 V 15 A

SSA564A136

F7

SRC50

250 V 20 A

SSA564A136A

F4

1. Preparing cable

(1) Selecting cable

Select the power source cable and connecting cable in accordance with the specifications mentioned below.

(a) Power source cable

  3cores* 2.5mm

2

 or more, conformed with 60245 IEC57

  When selecting the power source cable  length, make sure that voltage drop is less than 2 %.

  If the wire length gets longer, increase the wire diameter.

(b) Connecting cable

  4cores* 1.5mm

2

, conformed with 60245 IEC57

* 1 Earth wire is included (Yellow/Green).

(2) Arrange each wire length as shown below.

Make sure that each wire is stripped 10mm from the end.

<Power source cable>

<Connecting cable>

<Wire end>

Earth wire

40mm or more

30mm or more

40mm or more

Earth wire

30mm or more

10mm

(3) Attach round crimp-type terminal to each wire as shown in the below.

Select the size of round crimp-type terminal  after considering the specifications of terminal block and wire 

diameter.

10mm

Round crimp-type terminal

Sleeve

 CAUTION

Power source cable and connecting cable must conform to the specifications mentioned in the manual. 

Using cables with wrong specifications may result in unit malfunction.

2. Connecting cable 

(1) Remove the service cover.

(2) Connect the cables according to the instructions and figures given below.

 (a) Connect the earth wire of power source cable. 

   An earth wire must be connected before connecting the other wires of power source cable.

     Keep the earth wire longer than the remaining two wires of power source cable.

 (b) Connect the remaining two wires (N and L) of power source cable.

 (c)  Connect the wires of connecting cable. Make sure that for each wire, outdoor and indoor side 

terminal numbers match.

(3)  Fasten the cables properly with cable clamps so that no external force may work on terminal connec-

tions. 

   Moreover, make sure that cables do not touch the piping, etc. When cables are connected, make sure 

that all electrical components within the electrical component box are free of loose connector coupling 

or terminal connection.

<Circuit diagram>

N L

1 2/N 3

1 2/N 3

Circuit 

breaker

Earth 

leakage 

breaker

Earth

Power

source

Indoor  unit

Outdoor  unit

Connecting cable

Power 

source 

cable

<SRC20/25/35>

<SRC50>

Power 

source 

cable

Connecting 

cable

Connecting 

cable

Cable clamp

 

8. FINISHING WORK

1. Heating and condensation prevention

(1) Dress the connecting pipes (both liquid and gas pipes) with insulation to prevent it from heating and 

dew condensation. 

 Use the heat insulating material which can withstand 120 °C or higher temperature. Make sure that 

insulation is wrapped tightly around the pipes and no gap is left between them. 

(2) Wrap the refrigerant pipings of indoor unit with indoor unit heat insulation using tape. 

(3) 

Cover the flare-connected joints (indoor side) with the indoor unit heat insulation and wrap it with an 

insulation pad (standard accessory provided with indoor unit). 

(4) Wrap the connecting pipes, connecting cable and drain hose with the tape.

(2)

(3)

(4)

Tape

Insulation pad

Position it so that the slit area faces upward.

Connecting cable

Liquid pipe

Drain hose

Gas pipe

Insulation

Tape

NOTE

Locations where relative humidity exceeds 70 %, both liquid and gas pipes need to be dressed with 20 mm  

or thicker heat insulation materials.

2. Finishing work 

(1)  Make sure that the exterior portion of connecting pipes, connecting cable and drain hose is wrapped 

properly with tape. Shape the connecting pipes to match with the contours of the pipe assembly route.

(2)  Fix the pipe assembly with the wall using clamps and screws. Pipe assembly should be anchored 

every 1.5 m or less to isolate the vibration.

(3)  Install the service cover securely. Water may enter the unit if service cover is not installed properly, 

resulting in unit malfunction and failure. 

Pipe assembly

Screw

Clamp

 CAUTION

• Improper insulation can cause condensate (water) formation during cooling operation. 

  Condensate can leak or drip causing damage to household property.

• Poor heat insulating capacity can cause pipe outer surface to reach high temperature during heating 

operation. It can cause cable deterioration and personal injury. 

 CAUTION

Make sure that the connecting pipes do not touch the components within the unit. If pipes touch the 

internal components, it may generate abnormal sounds and/or vibrations.

 

9. INSTALLATION TEST CHECK POINTS

After finishing the installation work, check the following points again before turning on the power. 

Conduct test run (Refer to indoor unit installation manual) and ensure that the unit operates properly. 

Power source voltage complies with the rated voltage of air-conditioner.
Earth leakage breaker and circuit breaker are installed.

Power cable and connecting cable are securely fixed to the terminal block.

Both liquid and gas service valves are fully open.

No gas leaks from the joints of the service valves.
Indoor and outdoor side pipe joints have been insulated.

Drain hose (if installed) is fixed properly.

Screw of the service cover is tightened properly.

'20 • SRF-DB-310

-

 37 

-

Summary of Contents for SRC20ZS-W

Page 1: ...f the power source in the event of installation mainte nance or service If the power source is not switched off there is a risk of electric shock unit failure or personal injury Be sure to tighten the cables securely in terminal block and relieve the cables properly to prevent overloading the terminal blocks Loose connections or cable mountings can cause anomalous heat production or fire Do not pr...

Page 2: ... or snow accumulation the fol lowing measures are required 1 Location of strong wind Place the unit with its outlet side facing the wall Place the unit such that the direction of air from the outlet gets perpendicular to the wind direction Over 500mm Wind direction Wind direction 2 Location of snow accumulation Install the unit on the base so that the bottom is higher than snow cover surface Insta...

Page 3: ...charge can be calculated using the formula given below Additional refrigerant charge g Connecting pipe length m Factory charged length A m x 20 g m Model SRK SRR SRF35 FDTC Model SRF25 A Factory charged length m 15 10 NOTE If additional refrigerant charge calculation result is negative there is no need to remove the refrigerant If refrigerant recharge is required for the unit with connecting pipe ...

Page 4: ... may work on terminal connec tions Moreover make sure that cables do not touch the piping etc When cables are connected make sure that all electrical components within the electrical component box are free of loose connector coupling or terminal connection Circuit diagram N L 1 2 N 3 1 2 N 3 Circuit breaker Earth leakage breaker Earth Power source Indoor unit Outdoor unit Connecting cable Power so...

Page 5: ... power source is not switched off there is a risk of electric shock unit failure or personal injury a c e h t e v e i l e r d n a k c o l b l a n i m r e t n i y l e r u c e s s e l b a c e h t n e t h g i t o t e r u s e B bles properly to prevent overloading the terminal blocks Loose connections or cable mountings can cause anomalous heat production or fire h t i w t e k c o s e h t e r a h s r o...

Page 6: ...d out 1 Install drain elbow and drain grommet l a i r e t a m g n i k l u a c e t a u q e d a r o y t t u p h t i w t e m m o r g n i a r d d n a w o b l e n i a r d e h t d n u o r a l a e S 2 SRC20 25 35 40 50 60ZSX W Do not put a grommet on this hole This is a supplementary drain hole to discharge drain water when a large amount of it is gathered CAUTION Do not use drain elbow and drain grommet...

Page 7: ...ressure gauge Pressure gauge Gauge manifold Handle Hi Vacuum pump CAUTION To prevent vacuum pump oil from entering into the refrigerant system use a counterflow prevention adapter 5 Additional refrigerant charge Additional refrigerant charge is required only when connecting pipe length exceeds 15 m 5 1 Calculating additional refrigerant charge Additional refrigerant charge can be calculated using t...

Page 8: ...embly should be anchored ev ery 1 5m or less to isolate the vibration 3 Install the service cover securely Water may enter the unit if service cover is not installed properly resulting in unit malfunction and failure Pipe assembly Screw Clamp CAUTION Improper insulation can cause condensate water formation during cooling operation Condensate can leak or drip causing damage to household property Po...

Page 9: ...oor unit shall be stored in a room that has a minimum area of 4 0 m2 D WARNING RSA012A061B WALL TYPE AIR CONDITIONER R32 REFRIGERANT USED is leaked together with an external ignition source there is a possibility of ignition There is information included in the user s manual and or installation manual The user s manual should be read carefully A service personnel should be handing this equipment w...

Page 10: ...ts are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essential that electrical power is available before the task is commenced a Become familiar with the equipment and its operation b Isolate system electrically c Before attempting the procedure ensure that mechanical han...

Reviews: