4.9 Outline of automatic operation
(1) Determination of operating mode
After the indoor and outdoor fans operate at the 2nd sped and 3rd speed respectively for 20
seconds, the system checks the room temperature and outdoor air temperature to determine the
operating mode and the room temperature setting compensation value, and then enters the
automatic operation.
(2) The unit checks the temperature every hour after the start of operation and, if the result of
check is not the same as the previous operating mode, it will change the operating mode.
(3) When the unit is started again within one hour after the stop of automatic operation or when
the automatic operation is selected during heating, cooling or drying operation, the unit will
operate in the original operating mode.
(4)
Set temperature can be adjusted within the following range. There is the relationship as shown
below between the signals of the wireless remote controller and the set temperature.
Signals of wireless remote controller (indication)
-6
-5
-4
-3
-2
-1
0
+1
+2
+3
+4
+5
+6
Set
temp.
Cooling
18
19
20
21
22
23
24
25
26
27
28
29
30
Drying
18
19
20
21
22
23
24
25
26
27
28
29
30
Heating
20
21
22
23
24
25
26
27
28
29
30
31
32
4.10 Economical operation (ECONO button on remote controller: ON)
(1) When the ECONO button is pressed, the power is controlled for gentle operation in the status
which is not too cold or too hot. In this case, the temperature in the Cooling mode is higher
than the set temperature by 1.5ºC (increasing 0.5ºC per hour), and the temperature in the
Heating mode is lower than the set temperature by 2.5ºC (decreasing 0.5ºC per hour).
Model
Item
SRK25QA-S
SRK35QA-S
Operating mode
Cooling
Heating
Cooling
Heating
Inverter instruction
frequency
20~46 rps
20~60 rps
20~62 rps
20~76 rps
Rotate speed of
indoor fan
2nd, 4th speed
3rd, 5th speed
2nd, 4th speed
3rd, 5th speed
Rotate speed of
outdoor fan
3rd speed
4.11 Air blowing operation
(1) When the fresh air signal from the remote controller is received, the fresh air operation begins.
(2) The so-called “fresh air operation” refers to the air blowing operation in the whole machine
with filter.
Air flow switching
Automatic
Hi
Me
Lo
Economical
Instruction frequency HZ
0
Rotate speed of indoor fan
6th speed
5th speed
4th speed
3rd speed
2nd speed
Rotate speed of outdoor fan
-
4-way valve
Same as cooling
(3) In this control, the continuous transmission error protection function can be neglected.
(4) In the fresh air operation, all timing functions are effective.
Cooling
Drying
Heating
Room temperature
Outdoor temperature
Summary of Contents for SRC25QA-S
Page 10: ... 7 3 ELECTRICAL WIRING DIAGRAM 3 1 Circuit diagram 25QA S ...
Page 11: ... 8 3 2 Circuit diagram 35QA S ...
Page 22: ... 19 B Prevent Range I in jiggle operation from changing to Range C operation ...
Page 58: ... 55 12 Check method for outdoor unit 1 Circuit diagram of 25QA S outdoor unit ...
Page 59: ... 56 2 Circuit diagram of 35QA S outdoor unit ...
Page 81: ... 78 ...
Page 86: ... 83 RAC SRK35QA S PANEL FAN ASSY ...
Page 88: ... 85 20 21 RYD436A021 LOUVER ASSY 1 20 RYD436A020 LOUVER 12 21 RYD129A048 PLATE CONNECTING 2 ...
Page 92: ... 89 ...
Page 94: ... 91 ...
Page 98: ... ...
Page 100: ... 19 RYF937A002A CLAMP WIRE 1 ...