-22-
4.12 CLEAN operation control
About CLEAN operation:
In the cooling and drying mode, when the unit is turned off, the fan of the indoor unit will
continue to run for 120 minutes to discharge the water from the unit for the purpose of
mould-proof.
CLEAN setting
Example: Setting of CLEAN operation when the unit is turned off after cooling operation.
1: When the air conditioner is in the stop mode, press the ON/OFF button.
2: Press the MODE button to set the cooling mode.
3: Press the CLEAN button and CLEAN indication on the display will light up.
Cancelation of CLEAN operation
Press the CLEAN button and CLEAN indication on the display will disappear.
.
4.13 Electronic expansion valve (EEV) control function
(1) General control range: 0~470 pulse.
(2) The open loop control and area control are combined for EEV control.