(4) Procedure of failure diagnosis (when the air conditioner can run)
Note: (1) When only stop data is indicated, the air conditioner is normal. However, when the same
protection is triggered repeatedly (more than 3 times), which becomes the user’s
complaint, it should be judged according to the content of failure.
Confirm the content of failure of the user’s air conditioner.
Is the cause of error
confirmed?
No
No
No
Yes
Yes
Yes
Yes
No
Confirm the displaying of self-diagnosis.
See Page 37
Eliminate the cause of error and check the
operation situation.
Has the self-diagnosis been
conducted?
Use the maintenance mode to read the past
indication of self-diagnosis
See Page 40-43
Is there any history of
indication of self-diagnosis?
Use the maintenance mode to read the history
of stop due to the past protection control.
See Page 40-43
Is there any history of stop
due to protection control?
(1)
Specifically check the defective part against
the content of failure according to the check
method.
Replace the defective part and check the
operation situation.
The air conditioner is normal.
Summary of Contents for SRC25QA-S
Page 10: ... 7 3 ELECTRICAL WIRING DIAGRAM 3 1 Circuit diagram 25QA S ...
Page 11: ... 8 3 2 Circuit diagram 35QA S ...
Page 22: ... 19 B Prevent Range I in jiggle operation from changing to Range C operation ...
Page 58: ... 55 12 Check method for outdoor unit 1 Circuit diagram of 25QA S outdoor unit ...
Page 59: ... 56 2 Circuit diagram of 35QA S outdoor unit ...
Page 81: ... 78 ...
Page 86: ... 83 RAC SRK35QA S PANEL FAN ASSY ...
Page 88: ... 85 20 21 RYD436A021 LOUVER ASSY 1 20 RYD436A020 LOUVER 12 21 RYD129A048 PLATE CONNECTING 2 ...
Page 92: ... 89 ...
Page 94: ... 91 ...
Page 98: ... ...
Page 100: ... 19 RYF937A002A CLAMP WIRE 1 ...