-47-
(f) List of temperatures of compressor vent-pipe
Unit:
℃
* If there is no data recorded (the error code is normal), the information of each sensor is as
showed in the table below:
Name of sensor
Value displayed by the sensor when the error code is
normal
Temperature measured by
vent-pipe sensor
-64
℃
(Example): Temperature of compressor vent-pipe: “122
℃
”
* The temperature data of compressor vent-pipe should be two times the reading. (The following,
61 x 2 = “122
℃
”)
Does the buzzer sound?
(Sound means negative)
RUN lamp
(tens place)
TIMER lamp
(ones place)
Yes
(Sounds for
0.1 sec.)
No
(Not sound)
RUN lamp
(tens place)
TIMER lamp
(ones place)
1.5 sec.
0.5 sec.
0.5 sec.
11 sec. cycle
Sound of
buzzer
(Negative)
0.1 sec.
When the temperature is < 0, the buzzer will sound.
When the temperature is
≥
0, the buzzer will not sound.