'20 • SRF-SM-311
-
14
-
3) Reset condition
The outdoor air temperature (TH2) is lower than 11ºC
(h) Heating low outdoor temperature protective control
• Models SRF25, 35
(i) Operating conditions
When the outdoor air temperature (TH2) is -2°C or lower continues for 30 seconds while the compressor command speed
is other than 0 rps
(ii) Detail of operation
The lower limit compressor command speed is changed as shown in the figure below.
(iii) Reset conditions
When either of the following condition is satisfied
a) The outdoor air temperature (TH2) becomes 2ºC.
b) The compressor command speed is 0 rps.
• Model SRF50
(i) Operating conditions
When the outdoor air temperature (TH2) is 4ºC or lower continues for 30 seconds while the compressor speed is other
than 0 rps
(ii) Detail of operation
The lower limit compressor speed is change as shown in the figure below.
(iii) Reset conditions
When either of the following condition is satisfied
a) The outdoor air temperature (TH2) becomes 6ºC.
b) The compressor speed is 0 rps.
11
13
16
17
OFF
Upper 75 rps
Lower 40 rps
Upper 90 rps
Lower 30 rps
Outdoor air temperature(ºC)
-10
-8
-2
2
Lower limit 45 (SRF35 : 55) rps
Lower limit 40 rps
Normal operation
Outdoor air temperature (°C)
-4
-6
-8
-10
-12
-2
4
Lower limit 35 rps
Lower limit 45 rps
Lower limit 55 rps
Lower limit 35 rps
Normal operation
Outdoor air temperature (°C)
6