'14 • SRF-T-163
(f)
Heating high pressure control
(i) Purpose:
Prevents anomalous high pressure operation during heating.
(ii) Detector:
Indoor heat exchanger sensor (Th)
(iii) Detail of operation:
A
B
C
D
Indoor heat exchanger temperature(°C)
4rps
(1)
8rps
(2)
8rps
(2)
4rps
(1)
0rps
After lapse of 20 (10) sec. or over
(3)
After lapse of 20 (10) sec. or over
(3)
After lapse of 20 (10) sec. or over
(3)
lower limit
speed 30(model SRF50:35)rps
(Example) Fuzzy
Notes () When the indoor heat exchanger temperature is in the range of B-C ºC, the speed is reduced by rps at each 0 (0) seconds.
() When the indoor heat exchanger temperature is in the range of C-D ºC, the speed is reduced by rps at each 0 (0) seconds. When the temperature
is D ºC or higher continues for minute, the compressor is stopped.
() When the indoor heat exchanger temperature is in the range of A-B ºC, if the compressor command speed is been maintained and the operation has
continued for more than 0 (0) seconds at the same speed, it returns to the normal heating operation.
() Indoor blower retains the fan tap when it enters in the high pressure control. Outdoor blower is operated in accordance with the speed.
() Value in ( ) are for the model SRF0.
¡
Temperature list
A
B
C
D
RPSmin < 50
50 <= RPSmin < 95
.
95 <= RPSmin < 97
.
- .
97 <= RPSmin < 104
.
. - .
- .
104 <= RPSmin < 115
. - .
. -
. - .
115 <= RPSmin
.
.
Note () RPSmin: The lower one between the outdoor speed and the compressor command speed.
Models SRF,
A
B
C
D
RPSmin < 50
.
50 <= RPSmin < 115
- .
115 <= RPSmin < 120
-
- 0
.
120 <= RPSmin
0
.
Model SRF0
Unit : ºC
Note () RPSmin: The lower one between the outdoor speed and the compressor command speed
Unit : ºC
'09•SRK-DB-087D
(g) Heating overload protective control
(i) Indoor unit side
1) Operating conditions :
2) Detail of operation :
3) Reset conditions :
(ii) Outdoor unit side
1) Operating conditions :
2) Detail of operation
3) Reset conditions:
(i)
Operating conditions:
(ii)
Detail of operation:
(h) Heating low outdoor temperature protective control
(iii) Reset conditions:
-10
-8
-2
2
Lower limit 45 rps
Lower limit 40 rps
Normal operation
Outdoor air temperature(°C)
10
11
19
20
Normal operation
Protective control ON1
Protective control ON2
Outdoor air temperature(°C)
21
22
Normal operation
Protective
control
Outdoor air temperature(°C)
• Model SRK50
• Model 50
• Models SRK20 ~ 35
• Models SRF25, 35
(i)
ޓ
Operating conditions:
When the outdoor air temperature (TH2) is lower than 4ºC or 13ºC or higher continues for 30
seconds while the compressor command speed is other than 0 rps.
(ii)
ޓ
Detail of operation:
The lower limit compressor command speed is change as shown in the figure belo.
Lower limit 29 rps
Normal operation
4
6
Outdoor air temperature(°C)
Model SRK50
A
B
C
D
RPSmin < 40
40 <= RPSmin < 80
80 <= RPSmin < 90
90 <= RPSmin < 102
102 <= RPSmin
49
53
41
53 ~ 47
47 ~ 41
53
57
45
57 ~ 51
51 ~ 45
55
59
47
59 ~ 53
53 ~ 47
58
62
51
58
51
When the outdoor air temperature (TH2) is 22ºC or higher continues for 30 seconds while
the compressor command speed other than 0 rps.
a)
b)
c)
d)
Taking the upper limit of compressor command speed range at 60 rps, if the output speed obtained with the fuzzy
calculation exceeds the upper limit, the upper limit value is maintained.
The lower limit of compressor command speed is set to 40 rps and even if the calculated result becomes lower than
that after fuzzy calculation, the speed is kept to 40 rps. However, when the
thermo OFF, the speed is reduced to 0 prs.
rps.
1) Operating conditions :
2) Detail of operation
When the outdoor air temperature (TH2) is 11ºC or higher continues for 30 seconds while
the compressor command speed other than 0 rps.
a)
b)
c)
d)
Taking the upper limit of compressor command speed range at 78 rps, if the output speed obtained with the fuzzy
calculation exceeds the upper limit, the upper limit value is maintained.
The lower limit of compressor command speed is set to 30 rps and even if the calculated result becomes lower than
that after fuzzy calculation, the speed is kept to 30 rps. However, when the
thermo becomes OFF, the speed is
reduced to 0 prs.
rps.
.
3) Reset conditions:
.
1)
2)
30
Protective
control
ON1
ON2
Item
Compressor command speed
Low limit
30 rps
30 rps
Upper limit
78 rps
51 rps
It depends on compressor command speed
Outdoor fan speed
2nd
10
9
Summary of Contents for SRF25ZMXA-S
Page 2: ......
Page 3: ... 14 SRF T 163 TECHNICAL MANUAL ...
Page 12: ... 10 14 SRF T 163 3 Remote control Unit mm 60 26 167 a Wireless remote control ...
Page 93: ... 91 14 SRF T 163 WARING CAUTION 3 Super link E board SC ADNA E F ...
Page 94: ... 92 14 SRF T 163 ...
Page 100: ... 98 14 SRF T 163 CRCE0010 12 13 14 3 2 1 4 4 5 10 10 4 7 8 9 6 15 16 11 CONTROL PARTS SET ...
Page 106: ... 104 14 SRF T 163 CRCE0010 12 13 14 3 2 1 4 4 5 10 10 4 7 8 9 6 15 16 11 CONTROL PARTS SET ...
Page 112: ... 110 14 SRF T 163 CRCE0010 12 13 14 3 2 1 4 4 5 10 10 4 7 8 9 6 15 16 11 CONTROL PARTS SET ...
Page 114: ... 112 14 SRF T 163 CRBE0276 6 13 11 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY ...
Page 118: ... 116 14 SRF T 163 CRBE0276 6 13 11 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY ...
Page 122: ... 120 14 SRF T 163 CRBE0315 9 13 15 16 14 17 7 6 4 1 8 3 11 5 18 10 10 10 2 12 PANEL FAN ASSY ...