'12•SRK-T-137
When refrigerant piping exceeds 7.5m conduct additional refrigerant charge after refrigerant sweeping.
7.5m over 15m:Additional charge amount per meter = 10g/m
[Example]
How much amount of additional charge for 15m piping?
(15 – 7.5)m
×
10g/m=75g 75g for additional charge
♦
Additional refrigerant charge
Installation of wireless remote control
Insulation of connecting portion
Mounting method of battery
Earthing work
①
Cover the connection portion of the refrigerant piping with the
pipe cover and seal them.
If neglecting to do so, moisture occurs on the piping and water
will drip out.
②
Finishing and fixing
ⓐ
Tie up the piping with wrapping tape, and shape it so that it con-
forms to which the pipe is attached.
ⓑ
Fix them with clamps as right figure.
Vinyl tape
To cover the connecting portion with insula-
tion materials, cut upper portion and then seal
it with insulation materials.
Cover the exterior portion with cov-
ering tape and shape the piping so it
will match the contours of the route
that the piping to take. Also fix the
wiring and pipings to the wall with
clamps.
Insulation
Refrigerant piping
Electrical wiring
Covering tape
Drain hose
Tapping screw
-
-
+
+
•
Uncover the wireless remote control, and mount the bat-
teries [R03(AAA, Micro)
×
2 pieces] in the body regu-
larly.
(Fit the poles with the indication marks,
⊕
&
⊖
without
fail)
•
Earth work shall be carried out without fail in order to prevent electric shock and noise generation.
•
The connection of the earth cable to the following substances causes dangerous failures, therefore it shall never be done.
City water pipe, Town gas pipe, TV antenna, lightning conductor, telephone line, etc.
Trial run and operation
①
Conduct trial run after confirming that there is no gas leaks.
②
When conducting trial run set the remote control thermostat to continuous operation position. However when the power source is cut
off or when the unit’s operation switch is turned off or was turned to fan operation position, the unit will not go into operation in
order to protect the compressor.
③
Explain to the customer on the correct usage of the air-conditioner in simple layman’s terms.
④
Make sure that drain flows properly.
Battery
Cover
Fixing to pillar or wall
•
Conventionally, operate the wireless remote control by
holding in your hand.
•
Avoid installing it on a clay wall etc.
Screws
Summary of Contents for SRK-13CMS-2
Page 46: ... 45 12 SRK T 137 3 Wireless remote control Unit mm 60 17 3 150 Unit mm 60 17 3 150 ...
Page 71: ... 70 12 SRK T 137 4 Troubleshooting procedure If the air conditioner runs NO YES 71 ...
Page 79: ... 78 12 SRK T 137 ...
Page 108: ... 107 12 SRK T 137 MEMO ...
Page 114: ... 113 12 SRK T 137 MEMO ...
Page 117: ... 116 12 SRK T 137 CRBE0290 6 11 9 10 13 14 3 15 12 2 4 8 7 5 1 7 7 PANEL FAN ASSY ...
Page 121: ... 120 12 SRK T 137 CRBE0290 6 11 9 10 13 14 3 15 12 2 4 8 7 5 1 7 7 PANEL FAN ASSY ...
Page 125: ... 124 12 SRK T 137 CRBE0290 6 11 9 10 13 14 3 15 12 2 4 8 7 5 1 7 7 PANEL FAN ASSY ...
Page 129: ... 128 12 SRK T 137 CRBE0290 6 11 9 10 13 14 3 15 12 2 4 8 7 5 1 7 7 PANEL FAN ASSY ...
Page 133: ... 132 12 SRK T 137 CRBE0290 6 11 9 10 13 14 3 15 12 2 4 8 7 5 1 7 7 PANEL FAN ASSY ...
Page 137: ... 136 12 SRK T 137 CRBE0290 6 11 9 10 13 14 3 15 12 2 4 8 7 5 1 7 7 PANEL FAN ASSY ...
Page 141: ... 140 12 SRK T 137 CRBE0221 12 16 17 1 2 3 5 6 7 8 9 10 13 16 14 15 4 11 PANEL FAN ASSY ...