-
-
'12•SRK-T-137
Model
Item
SRK25CMS
Indoor unit
SRK25CMS
Outdoor unit
SRC25CMS
Cooling capacity (1)
W
7200
Power supply
1 Phase, 220V, 50Hz
Operation
data (1)
Power
consumption
Cooling
kW
2.12
Running
current
Cooling
A
9.8
Inrush current
45
COP
Cooling
3.40
Noise
level
Cooling
Sound level
dB(A)
Hi : 50 Me : 46 Lo : 43
55
Power level
dB
60
67
Exterior dimensions (Height x Width x Depth)
mm
318 x 1098 x 248
750 x 880 x 340
Exterior appearance
(Munsell color)
Fine snow
(8.0Y 9.3/0.1) near equivalent
Stucco white
(4.2Y 7.5/1.1) near equivalent
Net weight
kg
17
56
Refrigerant
equipment
Compressor type & Q'ty
—
2JS386D5CA02 (Rotary type) x 1
Motor (Starting method)
kW
—
1.8 (Line starting)
Refrigerant oil
0.7 (ATMOS NM56M or SONISO 4GDID)
Refrigerant (3)
kg
R22 1.05 (Pre-Charged up to the piping length of 7m)
Heat exchanger
Slit fins & inner grooved tubing
Aluminium heat-exchanger
Refrigerant control
Capillary tubes + Electronic expansion valve
Deice control
Microcomputer control
Air handling
equipment
Fan type & Q'ty
Tangential fan x 1
Propeller fan x 1
Motor
W
40
75
Air flow
Cooling
m
3
/min
Hi : 20.0 Me : 17.0 Lo : 14.0
60
Fresh air intake
Not possible
—
Air filter, Quality / Quantity
Polypropylene net (washable) x 2
—
Shock & vibration absorber
—
Cushion rubber (for compressor)
Operation
control
Operation switch
Wireless-Remote control
—
Room temperature control
Microcomputer thermostat
—
Operation Display
RUN : Green, TIMER : Yellow, HI POWER : Green,
3D AUTO : Green
Safety devices
Compressor overheat protection,
Frost protection, Serial signal error protection, Fan motor error protection,
Installation
data
Refrigerant piping size (O.D)
mm
Liquid line :
φ
6.35 (1/4") Gas line :
φ
15.88 (5/8")
connecting method
Flare connecting
Attached length of piping
m
Liquid line : 0.70
Gas line : 0.63
—
Insulation for piping
Necessary (Both sides), independent
Refrigerant line (one way) length
m
Max. 25
Vertical height difference between
outdoor unit and indoor unit
Max.15 (Outdoor unit is higher)
Max.15 (Outdoor unit is lower)
Drain hose
Connectable (VP 16)
—
Power cable
2m (3 Cores wih Earth)
Recommended breaker size
A
20
Connection wiring
Size x Core number
1.5mm
2
x 4 cores (Including earth cable)
Connecting method
Terminal block (Screw fixing type)
Accessories (included)
Mounting kit
Option parts
—
Note (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO-T1 , JIS C 9612
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) The operation data are applied to the 220V districts respectively.
(4) The refrigerant quantity to be charged includes the refrigerant in 7m connecting piping.
(Purging is not required even for the short piping.)
The pipe length is 7.5m.
Summary of Contents for SRK-13CMS-2
Page 46: ... 45 12 SRK T 137 3 Wireless remote control Unit mm 60 17 3 150 Unit mm 60 17 3 150 ...
Page 71: ... 70 12 SRK T 137 4 Troubleshooting procedure If the air conditioner runs NO YES 71 ...
Page 79: ... 78 12 SRK T 137 ...
Page 108: ... 107 12 SRK T 137 MEMO ...
Page 114: ... 113 12 SRK T 137 MEMO ...
Page 117: ... 116 12 SRK T 137 CRBE0290 6 11 9 10 13 14 3 15 12 2 4 8 7 5 1 7 7 PANEL FAN ASSY ...
Page 121: ... 120 12 SRK T 137 CRBE0290 6 11 9 10 13 14 3 15 12 2 4 8 7 5 1 7 7 PANEL FAN ASSY ...
Page 125: ... 124 12 SRK T 137 CRBE0290 6 11 9 10 13 14 3 15 12 2 4 8 7 5 1 7 7 PANEL FAN ASSY ...
Page 129: ... 128 12 SRK T 137 CRBE0290 6 11 9 10 13 14 3 15 12 2 4 8 7 5 1 7 7 PANEL FAN ASSY ...
Page 133: ... 132 12 SRK T 137 CRBE0290 6 11 9 10 13 14 3 15 12 2 4 8 7 5 1 7 7 PANEL FAN ASSY ...
Page 137: ... 136 12 SRK T 137 CRBE0290 6 11 9 10 13 14 3 15 12 2 4 8 7 5 1 7 7 PANEL FAN ASSY ...
Page 141: ... 140 12 SRK T 137 CRBE0221 12 16 17 1 2 3 5 6 7 8 9 10 13 16 14 15 4 11 PANEL FAN ASSY ...