'13•SRK-T-141
When refrigerant piping exceeds 7.5m conduct additional refrigerant charge after refrigerant sweeping.
Model SRK05CM
7.5m over 15m:Additional charge amount per meter = 10g/m
[Example]
How much amount of additional charge for 15m piping?
(15 – 7.5)m
×
10g/m=75g 75g for additional charge
♦
Additional refrigerant charge
When refrigerant piping exceeds 5m conduct additional refrigerant charge after refrigerant sweeping.
5m over 15m:Additional charge amount per meter = 10g/m
[Example]
How much amount of additional charge for 15m piping?
(15 – 5)m
×
10g/m=100g 100g for additional charge
Installation of remote control switch
Insulation of connecting portion
Mounting method of battery
Earthing work
①
Cover the connection portion of the refrigerant piping with the pipe
cover and seal them.
If neglecting to do so, moisture occurs on the piping and water will
drip out.
②
Finishing and
fi
ⓐ
Tie up the piping with wrapping tape, and shape it so that it conforms
to which the pipe is attached.
ⓑ
Fix them with clamps as right
fi
gure.
Vinyl tape
To cover the connecting portion with insulation
materials, cut upper portion and then seal it with
insulation materials.
Cover the exterior portion with
covering tape and shape the piping
so it will match the contours of the
route that the piping to take. Also
fi
x the wiring and pipings to the wall
with clamps.
Insulation
Refrigerant piping
Electrical wiring
Covering tape
Drain hose
Tapping screw
+
+
-
-
•
Uncover the remote control switch, and mount the batteries
[R03(AAA, Micro)
×
2 pieces] in the body regularly.
(Fit the poles with the indication marks,
+
&
-
without
fail)
•
Earth work shall be carried out without fail in order to prevent electric shock and noise generation.
•
The connection of the earth cable to the following substances causes dangerous failures, therefore it shall never be done.
City water pipe, Town gas pipe, TV antenna, lightning conductor, telephone line, etc.
Trial run and operation
①
Conduct trial run after con
fi
rming that there is no gas leaks.
②
When conducting trial run set the remote control thermostat to continuous operation position. However when the power source is cut
off or when the unit’s operation switch is turned off or was turned to fan operation position, the unit will not go into operation in order
to protect the compressor.
③
Explain to the customer on the correct usage of the air-conditioner in simple layman’s terms.
④
Make sure that drain flows properly.
Battery
Cover
Fixing to pillar or wall
•
Conventionally, operate the wireless remote control by
holding in your hand.
•
Avoid installing it on a clay wall etc.
Screws
Models SRK05CM-3, 09CM-3, 09CM-4, 09CM-5
SRK05CMP-3, 09CMP-3, 09CMP-4
Summary of Contents for SRK05CM
Page 2: ... 13 SRK T 141 TECHNICAL MANUAL ...
Page 73: ... 72 13 SRK T 141 CRBE0358 7 4 12 6 1 14 15 7 6 5 8 3 6 9 6 13 11 10 2 PANEL FAN ASSY ...
Page 77: ... 76 13 SRK T 141 CRBE0358 7 4 12 6 1 14 15 7 6 5 8 3 6 9 6 13 11 10 2 PANEL FAN ASSY ...
Page 81: ... 80 13 SRK T 141 CRBE0361 7 4 12 6 1 14 15 7 6 5 8 3 6 9 6 13 11 10 2 PANEL FAN ASSY ...
Page 85: ... 84 13 SRK T 141 CRBE0358 7 4 12 6 1 14 15 7 6 5 8 3 6 9 6 13 11 10 2 PANEL FAN ASSY ...
Page 89: ... 88 13 SRK T 141 CRBE0358 7 4 12 6 1 14 15 7 6 5 8 3 6 9 6 13 11 10 2 PANEL FAN ASSY ...