background image

– 26 –

Safety precautions

When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping
length, height differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces.

We recommend you to read this “SAFETY PRECAUTIONS” carefully before the installation work in order to gain full advantage of the func-
tions of the unit and to avoid malfunction due to mishandling.

The precautions described below are divided into 

WARNING

  and  

CAUTION

 . The matters with possibilities leading to serious conse-

quences such as death or serious personal injury due to erroneous handling are listed in the  

WARNING

  and the matters with possibilities

leading to personal injury or damage of the unit due to erroneous handling including probability leading to serious consequences in some cases
are listed in 

CAUTION

 . These are very important precautions for safety. Be sure to observe all of them without fail.

Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the operating methods as well as the
maintenance methods of this equipment to the user according to the owner’s manual.

Keep the installation manual together with owner’s manual at a place where any user can read at any time. Moreover if necessary, ask to hand
them to a new user.

For installing qualified personnel, take precautions in respect to themselves by using suitable protective clothing, groves, etc., and then perform
the installation works.

Please pay attention not to fall down the tools, etc. when installing the unit at the high position.

If unusual noise can be heard during operation, consult the dealer.

Symbols which appear frequently in the text have the following meaning:

Observe instructions
with great care

Strictly prohibited

Provide proper earthing

 WARNING

Installation must be carried out by the qualified installer.

If you install the system by yourself, it may cause serious trouble such as
water leaks, electric shocks, fire and personal injury, as a result of a system
malfunction.

Install the system in full accordance with the instruction manual.

Incorrect installation may cause bursts, personal injury, water leaks, electric
shocks and fire.

Be sure to use only for household and residence.

If this appliance is installed in inferior environment such as machine shop
and etc., it can cause malfunction.

Use the original accessories and the specified components for installation.

If parts other than those prescribed by us are used, It may cause water leaks,
electric shocks, fire and personal injury.

Install the unit in a location with good support.

Unsuitable installation locations can cause the unit to fall and cause material
damage and personal injury.

Ensure the unit is stable when installed, so that it can withstand earth-
quakes and strong winds.

Unsuitable installation locations can cause the unit to fall and cause material
damage and personal injury.

Ventilate the working area well in the event of refrigerant leakage dur-
ing installation.

If the refrigerant comes into contact with naked flames, poisonous gas is
produced.

When installing in small rooms, take prevention measures not to exceed
the density limit of refrigerant in the event of leakage.

Consult the expert about prevention measures. If the density of refrigerant
exceeds the limit in the event of leakage, lack of oxygen can occur, which
can cause serious accidents.

After completed installation, check that no refrigerant leaks from the system.

If refrigerant leaks into the room and comes into contact with an oven or
other hot surface, poisonous gas is produced.

Use the prescribed pipes, flare nuts and tools for R410A.

Using existing parts (for R22 or R407C) can cause the unit failure and seri-
ous accidents due to burst of the refrigerant circuit.

Tighten the flare nut by torque wrench with specified method.

If the flare nut were tightened with excess torque, this may cause burst and
refrigerant leakage after a long period.

Do not open the operation valves for liquid line and gas line until com-
pleted refrigerant piping work, air tightness test and evacuation.

If the compressor is operated in state of opening operation valves before
completed connection of refrigerant piping work, air can be sucked into re-
frigerant circuit, which can cause bust or personal injury due to anomalously
high pressure in the refrigerant.

Do not put the drainage pipe directly into drainage channels where poi-
sonous gases such as sulphide gas can occur.

Poisonous gases will flow into the room through drainage pipe and seriously
affect the user’s health and safety.

Ensure that no air enters in the refrigerant circuit when the unit is in-
stalled and removed.

If air enters in the refrigerant circuit, the pressure in the refrigerant circuit
becomes too high, which can cause burst and personal injury.

Do not processing, splice the power cord, or share a socket with other
power plugs.

This may cause fire or electric shock due to defecting contact, defecting in-
sulation and over-current etc.

The electrical installation must be carried out by the qualified electri-
cian in accordance with “the norm for electrical work” and “national
wiring regulation”, and the system must be connected to the dedicated
circuit.

Power supply with insufficient capacity and incorrect function done by im-
proper work can cause electric shocks and fire.

Be sure to shut off the power before starting electrical work.

Failure to shut off the power can cause electric shocks, unit failure or incor-
rect function of equipment.

Be sure to use the cables conformed to safety standard and cable
ampacity for power distribution work.

Unconformable cables can cause electric leak, anomalous heat production or
fire.

This appliance must be connected to main power supply by means of a
circuit breaker or switch (fuse:16A) with a contact separation of at least
3mm.

When plugging this appliance, a plug conforming to the norm
IEC60884-1 must be used.

Use the prescribed cables for electrical connection, tighten the cables
securely in terminal block and relieve the cables correctly to prevent
overloading the terminal blocks.

Loose connections or cable mountings can cause anomalous heat production
or fire.

Arrange the wiring in the control box so that it cannot be pushed up
further into the box. Install the service panel correctly.

Incorrect installation may result in overheating and fire.

Be sure to fix up the service panels.

Incorrect fixing can cause electric shocks or fire due to intrusion of dust or
water.

Be sure to switch off the power supply in the event of installation, inspec-
tion or servicing.

If the power supply is not shut off, there is a risk of electric shocks, unit
failure or personal injury due to the unexpected start of fan.

Stop the compressor before disconnecting refrigerant pipes in case of
pump down operation.

If disconnecting refrigerant pipes in state of opening operation valves before
compressor stopping, air can be sucked, which can cause burst or personal
injury due to anomalously high pressure in the refrigerant circuit

Only use prescribed optional parts. The installation must be carried out
by the qualified installer.

If you install the system by yourself, it can cause serious trouble such as
water leaks, electric shocks, fire.

Do not bundling, winding or processing for the power cord. Or, do not
deforming the power plug due to tread it.

This may cause fire or heating.

Do not vent R410A into the atmosphere : R410A is a fluorinated green-
house gas, covered by the Kyoto Protocol with Global Warming Poten-
tial (GWP)=1975.

Do not run the unit with removed panels or protections.

Touching rotating equipments, hot surfaces or high voltage parts can cause
personal injury due to entrapment, burn or electric shocks.

Do not perform any change of protective device itself or its setup condition.

The forced operation by short-circuiting protective device of pressure switch
and temperature controller or the use of non specified component can cause
fire or burst.

Carry out the electrical work for ground lead with care.

Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line’s ground lead. Incorrect grounding can cause unit faults such
as electric shocks due to short-circuiting.

Summary of Contents for SRK10YL-S

Page 1: ...restasi penghawa dingin yang terbaik dan penggunaan yang berpanjangan sila baca dan fahami buku panduan pengguna ini dengan sepenuhnya sebelum menggunakan alat penghawa dingin ini Selepas membaca buku panduan ini sila letakkan buku panduan ini di tempat yang selamat Sila rujuk kepada buku panduan ini jika anda mempunyai apa apa soalan tentang pengendalian alat ini ataupun semasa keadaan yang luar ...

Page 2: ...ion procedure 11 ON TIMER operation procedure 12 SLEEP operation ON TIMER operation procedure 12 PROGRAM TIMER operation procedure 13 Present time setting procedure 13 HIGH POWER ECONOMY operation procedure 14 Concerning CLEAN operation 15 Emergency run operation 15 Power blackout auto restart function 15 Installation location setting 16 Remote control handling procedure 17 When the operation fail...

Page 3: ...arth cable Incorrect in stallation of the earth cable may produce an electric shock CAUTION DANGER OPERATION PRECAUTIONS Do not expose yourself to the cooling air for a long period Do not insert anything into the air inlet DANGER The appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge un less they ...

Page 4: ... electrical parts or the unit s motor Consult your dealer for repairs If you notice anything abnormal smell of burning etc stop the system turn off the power supply and consult your dealer In case the air conditioner is relo cated elsewhere contact your dealer or a professional fitter If the air conditioner fails to cool or warm the room it may have a refrigerant leakage Contact your dealer If ref...

Page 5: ...F They can be set as desired Page 13 When using the timer to switch on the sys tem should become operational shortly be fore the set time depending on the room temperature so that the desired temperature should be reached at the set time Amenity facility TIMER procedure SWING FLAP Flap moves up and down continuously SWING LOUVER Louver moves left and right continuously MEMORY FLAP FLAP OR LOUVER S...

Page 6: ...ss remote control holder OUTDOOR UNIT Air inlet panel Unit indication section and remote control signal receiver Air cleaning filter Air filter Wireless remote control Drain hose Left right air flow adjustment louver Up down air flow direction adjustment flap Air outlet Unit operation switch Room temperature detector Refrigerant piping connection electric flex Air outlet Outdoor unit fan Heat exch...

Page 7: ...se the panel When removing the air inlet panel for internal cleaning or others open the panel by 80 degrees and then pull it to this side In emergencies this button can be used for turning on off the unit when remote control is not available Page 15 Removal installation of air inlet panel 3D AUTO light green Illuminates during 3D AUTO operation HI POWER light green Illuminates during HIGH POWER op...

Page 8: ...on RESET switch Switch for resetting microcomputer and setting time Page 13 17 Indication section SLEEP indicator Indicates during SLEEP operation TEMPERATURE indicator Indicates set temperature Does not indicate temperature when operation mode is on AUTO FAN SPEED indicator Indicates set air flow rate with lamp CLEAN indicator Indicates during CLEAN operation ON OFF TIMER indicator Indicates duri...

Page 9: ...n the room temperature when switched on Air flow direction adjustment proce dure Page 10 1 When a change in temperature is desired Press the or button Air is not blown out during the opera tion Page 21 If you don t want the AUTO mode program change to COOL DRY or FAN instead of AUTO Page 9 AUTO mode can be oper ated by simply pressing the ON OFF button To stop Press the ON OFF button When the unit...

Page 10: ...Standard 4 3 To stop Press the ON OFF button Air is not blown out during the operation Page 21 NOTE 2 1 Air conditioner operating conditions Use within the following operational range Operating outside of this range may result in the protection devices being activated preventing the unit from working Cooling operation Outside temperature Approximately 21 to 43 C Inside temperature Approximately 21...

Page 11: ...eration is started DANGER Avoid constant airflow to the body for hours on end CAUTION When in COOL or DRY operation do not operate for hours on end with the air flow blowing straight down Otherwise condensation may appear on the outlet grill and drip down Do not try to adjust the flaps and louvers by hand as the control angle may change or the flap or louver may not close properly Horizontal blowi...

Page 12: ...s switched in the order of 0 00 23 50 23 40 Units of ten minutes 23 00 22 50 Set at 22 30 3 The unit stops automatically at the end of the set period of time If it is stopped perform the operations starting with STEP 1 and if running start with STEP 2 Changing of set time Set to a new time by using SLEEP button SLEEP operation procedure The unit stops automatically at the end of the set period of ...

Page 13: ...ge 11 Set to ON TIMER operation setting Set by the above mentioned ON TIMER operation procedure Set to The setting of the lighting of the timer light yellow of this unit is complete h After the SLEEP operation set time has elapsed the operation stops and it starts from 5 to 60 minutes before the ON TIMER s time The timer light is not lit at the ON TIMER s time Changing of set time Set a new time b...

Page 14: ...on The indication changes from blinking to steady lighting and the setting is complete 1 3 Changing of set time Set a new time by using the OFF TIMER or ON TIMER button About Amenity facilities Amenity facilities enable to start the operation a little earlier so that the room should approach optimum temperature at ON time when the operation is started by ON TIMER Mechanism The room temperature is ...

Page 15: ...ot available during the DRY the program timer operations and 3D AUTO operation During ON timer operation HIGH POWER operation will start when the ON time is reached When the following operations are conducted HIGH POWER op eration will be canceled 1 When the HI POWER ECONO button is pressed again 2 When the operation mode is changed 3 When it has been 15 min since HIGH POWER opera tion has started...

Page 16: ... is not used Operation program OPERATION MODE AUTO FAN SPEED AUTO AIR FLOW AUTO Operation starts by pressing the unit ON OFF button it stops if you press the button again Unit ON OFF button Power blackout auto restart function What is power blackout auto restart function Power blackout auto restart function is a function that records the operational status of the air conditioner immediately prior ...

Page 17: ...s set Press within 60 seconds of setting the installation location while the installation location setting display illuminates Press within 60 sec Air conditioner installation location and airflow range The diagram below indicates the airflow ranges corresponding to the air conditioner s installation location Consider your room s layout and set the airflow range to maximize conditioning effectiven...

Page 18: ...the tip of a ballpoint pen 1 2 3 Attention to the and marks Press the reset switch with the tip of a ballpoint pen The time setting mode is indicated Page 13 4 Don t drop the remote control Handle with care Don t go near high temperature places such as an electric carpet or stove Do not place heavy objects on the remote control or step on it Warning note for remote control handling Don t put any o...

Page 19: ... once every two week Don t use the following articles Hot water 40 C or more It may deform or discolour the unit Petrol paint thinner benzine or polishing agents etc They may deform or scratch the unit Don t spill water Do not touch the aluminum fins on the heat exchanger Stand firmly on a stepladder or other stable object when removing the inlet panel and filter Cleaning If the filter is very dir...

Page 20: ...er about 1 year of use However the actual replacement period may vary depending on the conditions in which the filter is used Remove the photocatalytic washable deodorizing filter from the filter holder and inspect the filter Periodically remove any dust or dirt from the photocatalytic washable deodoriz ing filter If the photocatalytic washable deodorizing filter is particularly dirt it may be was...

Page 21: ...ce is damaged it must only be replaced by a repair shop appointed by the manufacturer because special purpose tools are required Suitable installation position Is there any obstruction in front of the indoor unit preventing proper ventilation and functioning Don t install the unit in any of the following places Where there is a danger of leaking inflammable gases Where there is substantial splashi...

Page 22: ...e air outlet grills and start dripping You hear a slight gurgling sound This is caused by refrigerating liquid moving within the unit You hear a slight cracking sound This is caused by heat expansion or contraction Remote control signals may not be received if the signal receiver on the air conditioner is exposed to direct sunlight or other bright light If so cut out the sunlight or reduce the oth...

Page 23: ...t is observed when the ON OFF but ton is pressed even after turning off the power switch and restarting the operation after 3 minutes the faulty move ment does not disappear A switch does not activate properly You hear a strange noise during op eration 3 minutes go by but why Fuse often blows The RUN and TIMER lights on the unit indication section blink quickly 0 5 sec ON 0 5 sec OFF and don t wor...

Page 24: ...essor locking open phase on compressor output shortcircuit on power transistor closed service valve Defective power supply Broken signal wire defective in outdoor unit boards Power transistor error Broken power transistor Current cut Trouble of outdoor unit Over current Overload operation overcharge Over heat of compressor Error of signal transmission Outdoor fan motor error Defective fan motor po...

Page 25: ... 24 ...

Page 26: ...ndoor unit 29 Installation of outdoor unit 32 Connection of refrigerant pipings 32 How to relocate or dispose of the unit 33 Installation of remote control switch 34 Earthing work 34 Trial run and operation 34 Installations test check points 34 INSTALLATION DIRECTIONS INSTALLATION DIRECTIONS ...

Page 27: ...lves for liquid line and gas line until com pleted refrigerant piping work air tightness test and evacuation If the compressor is operated in state of opening operation valves before completed connection of refrigerant piping work air can be sucked into re frigerant circuit which can cause bust or personal injury due to anomalously high pressure in the refrigerant Do not put the drainage pipe dire...

Page 28: ...outdoor unit It can cause remarkable decrease in performance corrosion and damage of components malfunction and fire Do not install the indoor unit in the locations listed below Be sure to install the indoor unit according to the installation manual for each model because each indoor unit has each limitation Locations with any obstacles which can prevent inlet and outlet air of the unit Locations ...

Page 29: ...ear the bedroom and the like so that the operation noise will cause no trouble A place where there is possibility of flammable gas leakage A place exposed to strong wind 5 Blowing out port and suction port on the back side of the unit can be installed at a distance of 10cm from walls In case the barrier is 1 2m or above in height or is overhead the sufficient space between the unit and wall shall ...

Page 30: ... 585 102 5 133 5 450 206 5 202 450 138 44 5 43 2 39 3 200 15 Limitations for one way piping length and vertical height difference Model SRK10YL S SRK18YL S Item SRK13YL S Total one way piping length Max 15 m Max 25 m Vertical height difference h Max 10 m Max 15 m r h Drilling of holes and fixture sleeve Option parts Inserting sleeve Note 1 Drill a hole with incline of 5 degree from indoor side to ...

Page 31: ...g wire by wiring clamp e Attach the lid f Close the air inlet panel 2 Shaping the pipe 3 Taping of the exterior Hold the bottom of the pipe and change its direction before stretching it and shaping it Tape only the portion that runs through the wall Always tape the crossover wires with the pipe 4 Cautions when piping from the left and the rear center of the unit Top View Remove the screw and drain...

Page 32: ...f air inlet panel Set screws 1 Removing Remove the 2 set screws Move the lower part of the panel forward and push upwards to remove Remove the 3 latches in the upper section 2 Fitting Do remove the air filter Cover the body with the front panel Tighten the 2 set screws Fit the air filter Carry out in the above order 1 To open pull the panel at both ends of lower part and release latches then pull ...

Page 33: ...e note that measurement B protrusion from the flaring block will vary depending on the type of a flare tool in use If a conventional flare tool is used please use a copper pipe gauge or a similar instrument to check protrusion so that you can keep measurement B to a correct value Copper pipe diameter Clutch type flare tool f or R410A Conventional R22 flare tool Clutch type Wing nut type Measuremen...

Page 34: ... Vacuum pump Vacuum pump adapter Anti reverse flow type Designed specifically for R410A Charge hose Designed specifically for R410A Check joint 0 1MPa 76cmHg Handle Lo Operation valve Operation valve two way valve Operation valve cap Operation valve cap Operation valve cap tightening torque N m Check joint blind nut tightening torque N m ø6 35 1 4 ø9 52 3 8 10 12 ø12 7 1 2 25 35 20 30 Operation va...

Page 35: ... Make sure that drain flows properly Battery Cover Fixing to pillar or wall Conventionally operate the wireless remote control by holding in your hand Avoid installing it on a clay wall etc Screws CAUTION Do not use new and old batteries together Installations test check points Check the following points again after completion of the installation and before turning on the power Conduct a test run ...

Reviews: