123
-
Output voltage
(ACV)
(Example)
Self-diagnosis display : Flashes 2 times
Measure in this section
Operation SW ON
8 ~ 10 sec.
0
1
◆
Power transistor inspection procedure
[Use a tester with a needle indicator for the inspection. (Do not use a digital tester. Check in the AC 300 volt range.)]
1) If there is a self-diagnosis display, inspect the compressor system (burns, wiring mistakes, etc.). If no problems are found,
check the output of the power transistor.
2) Output inspection procedure
Disconnect the terminals for the compressor.
If an output such as the one shown in the fig-
ure on the right can be measured, the power
transistor and the circuit board for the out-
door unit are normal.
* For about 50 seconds. After being switched on, there
will be a delay of approximately one minute depending
on the conditions.
(k)
How to make sure of remote control
Note (1) Check method of remote control
(a)
Press the reset switch of the remote control.
(b)
If all LCD are displayed after one (1) display, it is basically normal.
(1)
Is remote
control normal?
YES
Again pushing
operating switch
Operating the unit?
NO
Does unit ON/OFF
button operates?
Operating the unit.
NO
NO
YES
YES
Remote control
defects
Abnormality is not
found.
Replace the display.
Control problem on
main unit
Is the unit
operable with remote
control?
Defective remote
control
NO
YES
Normal
Summary of Contents for SRK13ZEV-S4
Page 2: ...TECHNICAL MANUAL 1 SRK13ZEV S4 2 2 SRK22ZEV S4 60 1 ...
Page 126: ...PARTS LIST INDOOR UNIT SRK13ZEV S4 SRK22ZEV S4 OUTDOOR UNIT SRC13ZEV S4 SRC22ZEV S4 125 ...
Page 134: ...MEMO 133 ...
Page 137: ... 136 CRBE0226 1 3 4 2 5 6 7 8 9 10 11 12 13 PANEL FAN ASSY ...
Page 145: ...ROOM AIR CONDITIONING TECHNICAL MANUAL PARTS LIST Manual No 06 SRK T 054 ...