Outline of cooling operation
(a)
Operation of major functional components in cooling mode
Item
Indoor fan motor
ON
ON
OFF
Flaps
ON or OFF
ON or OFF
Stop position control
Display
Lights up
Lights up
Lights up or flashes
52C
ON
ON
OFF after stop mode
Outdoor fan motor
OFF
ON
OFF
4-way valve
Depending on the stop mode
OFF
Depending on the stop mode
Electronic expansion valve
Depending on the EEV control
Solenoid valve
OFF
OFF
OFF
When the inverter
speed is 0rps
When the inverter speed
is other than 0rps
When the inverter speed is 0rps
due to an anomalous stop
Functional
components
(c)
Detail of control in each mode (Pattern)
(i)
Fuzzy operation
During the fuzzy operation, the air flow and the inverter speed are controlled by calculating the difference between the room
temperature setting correction temperature and the suction air temperature.
(ii)
Cooling thermostat operation
1) Operating conditions
During the cooling fuzzy operation or when the speed obtained by the fuzzy calculation is less than -24 rps.
2) Detail of operation
(b)
Air flow selection
(i)
Speed of inverter changes within the range of selected air flow.
(ii)
When any protective function actuates, the operation is performed in the mode corresponding to the function.
(iii)
Outdoor blower is operated in accordance with the inverter command speed.
(iii) Cooling “HI POWER” operation
(HI POWER button on remote control: ON)
The unit is operated continuously for 15 minutes regardless of the setting temperature.
1) Detail of operation
Model
SRK13ZEV-S4
Item
Inverter speed
0 rps [Comp. stopped]
Indoor fan
Corresponds to fan speed switch.
Outdoor fan
Stop
Notes (1) Protective functions will actuate with priority even during the “HI POWER” operation.
(2) Room temperature is not adjusted during the “HI POWER” operation
Model
SRK13ZEV-S4
Item
Inverter speed
94rps
Indoor fan
7th speed
Outdoor fan
6th speed
Model
SRK13ZEVS4
Air flow selection
Inverter command speed
12~94rps
Air flow
Depends on inverter command speed.
Inverter command speed
12~94rps
Air flow
Depends on inverter command speed.
Inverter command speed
12~50rps
Air flow
Depends on inverter command speed.
Inverter command speed
12~30rps
Air flow
2nd speed fixed.
Auto
HI
MED
LO
Summary of Contents for SRK13ZEV-S4
Page 2: ...TECHNICAL MANUAL 1 SRK13ZEV S4 2 2 SRK22ZEV S4 60 1 ...
Page 126: ...PARTS LIST INDOOR UNIT SRK13ZEV S4 SRK22ZEV S4 OUTDOOR UNIT SRC13ZEV S4 SRC22ZEV S4 125 ...
Page 134: ...MEMO 133 ...
Page 137: ... 136 CRBE0226 1 3 4 2 5 6 7 8 9 10 11 12 13 PANEL FAN ASSY ...
Page 145: ...ROOM AIR CONDITIONING TECHNICAL MANUAL PARTS LIST Manual No 06 SRK T 054 ...