16
-
(iv) Cooling “JET” operation
(JET button on remote control: ON)
1) Detail of operation
2) Indoor fan control
The indoor fan is controlled as shown at right in accordance with the
difference between the room temperature and setting temperature.
However, the limit after increasing the speed by 1 speed is 8 speeds.
Model
SRK13ZEV-S4
Item
Inverter speed
12~96 rps
Air flow
Depends on inverter command speed
(9)
Outline of dehumidifying operation
(a)
Operation start control
For 20 seconds when each type of dehumidifying starts, during judgment each hour, for 3 minutes when switching operations,
when the indoor fan is at 4th speed, the outdoor fan is at 3rd speed dehumidifying operates and the indoor and outdoor temperatures
are detected. However, during operation, (except when the On timer is in the wait state) each type of dehumidifying operation
starts immediately.
(b)
Dehumidifying operation
After implementing operation start control, the operation content is determined in accordance with room temperature and the set
temperature.
If one hour passes following the decision on the dehumidifying operation mode, and after operation start control, the decision is
made for another dehumidification cooling operation, a heating oriented dehumidifying operation or a reheat dehumidifying.
(i)
Cooling oriented dehumidifying operation
1) Detail of operation
Note (1) When a JET operation signal is received from the remote control, the indoor unit’s fan speed is increased by 1 speed.
Model
SRK13ZEV-S4
Item
Inverter speed
60 rps
Indoor fan motor
4th speed
Outdoor fan motor
5th speed
4-way valve
OFF
Solenoid valve
OFF
2) Operation change conditions
After 3 minutes have passed since the start of a cooling oriented dehumidifying operation, when the room setting temperature
becomes less than 0 degree, the dehumidifying operation changes to reheat dehumidifying.
(ii)
Reheat dehumidifying
1) Operation range
The operation range is determined in accordance with the room temperature, setting temperature and humidity.
Temperature range
Humidity range
I
range
II
range
III
range
a range
A
range
A
range
B
range
b range
A
range
B
range
C
range
c range
B
range
B
range
C
range
Depends on inverter
command speed
1 speed up
2
3
Room temp. - Setting temp. (deg)
Low
-3
+3
High
Cooling oriented
dehumidifying
Heating oriented
dehumidifying
Reheat dehumidifying
Room temp. _ Setting temp. (deg)
c Range
b Range
a Range
45
50
55
Humidity (%)
III
Range
II
Range
I
Range
-2
+1
0
-1
Room Temp. – Setting Temp. (deg)
Summary of Contents for SRK13ZEV-S4
Page 2: ...TECHNICAL MANUAL 1 SRK13ZEV S4 2 2 SRK22ZEV S4 60 1 ...
Page 126: ...PARTS LIST INDOOR UNIT SRK13ZEV S4 SRK22ZEV S4 OUTDOOR UNIT SRC13ZEV S4 SRC22ZEV S4 125 ...
Page 134: ...MEMO 133 ...
Page 137: ... 136 CRBE0226 1 3 4 2 5 6 7 8 9 10 11 12 13 PANEL FAN ASSY ...
Page 145: ...ROOM AIR CONDITIONING TECHNICAL MANUAL PARTS LIST Manual No 06 SRK T 054 ...