75
-
Model
SRK22ZEV-S4
Item
Inverter command speed
64 rps
Indoor fan motor
8th speed
Outdoor fan motor
6th speed
(9)
Outline of cooling operation
(a)
Operation of major functional components in Cooling mode
Item
Indoor fan
ON
ON
OFF
Flap and louver
ON or OFF
ON or OFF
Stop position control
Display
Lights up
Lights up
Lights up or flashes
Outdoor fan motor
ON
4-way valve
Depending on the stop mode
OFF
Depending on the stop mode
Electronic expansion valve
Depending on the EEV control
When the inverter
speed is 0rps
When the inverter speed
is other than 0rps
When the inverter speed is 0rps
due to an anomalous stop
Functional
components
(b)
Air flow selection
(i)
Speed of inverter changes within the range of selected air flow.
(ii)
When any protective function actuates, the operation is performed in the mode corresponding to the function.
(iii)
Outdoor blower is operated in accordance with the inverter command speed.
(c)
Detail of control in each mode (Pattern)
(i)
Fuzzy operation
During the fuzzy operation, the air flow and the inverter command speed are controlled by calculating the difference between
the room temperature setting correction temperature and the suction air temperature.
(ii)
Cooling thermostat operation
1) Operating conditions
During the cooling fuzzy operation or when the inverter command speed obtained by the fuzzy calculation is less than -
24 rps.
2) Detail of operation
(iii) Cooling “HIGH POWER” operation
(HI POWER button on remote control: ON)
The unit is operated continuously for 15 minutes regardless of the setting temperature.
1) Detail of operation
Model
SRK22ZEV-S4
Item
Inverter command speed
0 rps [Comp. stopped]
Indoor fan motor
Corresponds to fan speed switch.
Outdoor fan motor
Stop
Notes (1) Protective functions will actuate with priority even during the “HIGH POWER” operation.
(2) Room temperature is not adjusted during the “HIGH POWER” operation
Model
SRK22ZEV-S4
Air flow selection
Inverter command speed
12~64rps
Air flow
Depends on inverter command speed.
Inverter command speed
12~64rps
Air flow
8th speed fixed
Inverter command speed
12~54rps
Air flow
6th speed fixed
Inverter command speed
12~40rps
Air flow
4th speed fixed
Inverter command speed
12~30rps
Air flow
2nd speed fixed
Auto
HI
MED
LO
ULO
Summary of Contents for SRK13ZEV-S4
Page 2: ...TECHNICAL MANUAL 1 SRK13ZEV S4 2 2 SRK22ZEV S4 60 1 ...
Page 126: ...PARTS LIST INDOOR UNIT SRK13ZEV S4 SRK22ZEV S4 OUTDOOR UNIT SRC13ZEV S4 SRC22ZEV S4 125 ...
Page 134: ...MEMO 133 ...
Page 137: ... 136 CRBE0226 1 3 4 2 5 6 7 8 9 10 11 12 13 PANEL FAN ASSY ...
Page 145: ...ROOM AIR CONDITIONING TECHNICAL MANUAL PARTS LIST Manual No 06 SRK T 054 ...