'16 • SRK-T-192
(9) Outline of cooling operation
(a) Operation of major functional components in cooling mode
(b) Detail of control in each mode (Pattern)
(i) Fuzzy operation
During the fuzzy operation, the air flow and the compressor command speed are controlled by calculating the difference
between the room temperature setting correction temperature and the suction air temperature.
ON
OFF
OFF
ON
OFF
(few minutes ON)
OFF
(few minutes ON)
ON
ON
ON
Thermostat ON
Thermostat OFF
Failure
Cooling
Compressor
Indoor fan motor
Outdoor fan motor
Model
Fan speed
23~96rps
23~96rps
23~62rps
23~38rps
SRK18YLV-S1
Auto
MED
HI
LO
(14)
Outline of dry (dehumidifying) operation
The purpose is "Dehumidification", and not to control the humidity to the target condition.
Indoor/outdoor unit control the operation condition to reduce the humidity, and also prevent over cooling.
(i) Indoor unit fan speed and compressor are controlled by the area which is selected by the temperature difference.
Indoor unit fan speed
Area
D
C
B
A
Me speed
Indoor unit
fan speed
Lo speed
STOP
Limited
(
Lower than
normal cooling operation
)
Compressor
Limited
speed
Minimum
(
Lower than the speed in”Area A”
)
STOP
Set temperature
Difference between set temperature and return temperature
When the outside temperature and room temperature is low for cooling operation, indoor unit can not operate in cooling, and
dehumidifying.
(a) Purpose of DRY mode
(b) Outline of control
(ii) The indoor unit check the current area by every 5 minutes, and operate by the next checking.
(c) Other
(10) Outline of dehumidifying (DRY) operation
Summary of Contents for SRK18YLV-S1
Page 2: ......
Page 3: ...TECHNICAL MANUAL ...
Page 9: ... 16 SRK T 192 3 Wireless remote control Unit mm 60 17 3 150 ...
Page 53: ... 50 16 SRK T 192 ...
Page 54: ... 51 16 SRK T 192 PARTS LIST INDOOR UNIT SRK18YLV S1 OUTDOOR UNIT SRC18YLV S1 ...
Page 59: ... 56 16 SRK T 192 CRBE0294 6 13 11 18 12 15 16 3 17 14 2 4 9 8 7 5 1 8 8 10 PANEL FAN ASSY ...