16
-
(c)
To accomplish rapid recovery from the thermostat off state, after the compressor and outdoor unit’s fan go OFF, the set
temperature is raised by 1ºC until 1 minute passes after the hot keep end temperature has been reached following restarting.
(5)
Hot spurt
(a)
For 40 minutes after a heating operation begins, the system runs with set temperature raised by 2ºC.
(b)
In the following cases, this function is canceled and does not activate afterwards.
1) When the compressor and outdoor unit fan have been turned OFF by the thermostat going off.
2) During high pressure control operation.
(6)
HIGH POWER operation (“HI POWER” button on the remote control : ON)
The system runs under the following conditions for 15 minutes without relation to the set temperature or the fan speed setting.
(7)
Defrost operation
(a)
Starting conditions (Defrost operation begins when all the following conditions are satisfied.)
1
40 minutes have passed since the heating operation began. (Accumulated operation time)
2
40 minutes have passed since the previous defrosting operation ended. (Accumulated operation time)
3
The outdoor unit heat exchanger sensor temperature is –5ºC or lower continuously for 3 minutes.
4
The difference between the outdoor air temperature sensor temperature and the outdoor heat exchange sensor tempera-
ture is => 4.5ºC.
5
The compressor is running.
Also, the number of times the compressor goes OFF is counted, and when it reaches 10 or more times, if the conditions
in
1
,
2
and
3
above (except that the outdoor heat exchanger sensor temperature is –1ºC), the defroster operation starts.
(b)
End conditions (when either of the following conditions is satisfied)
1
Outdoor heat exchanger sensor temperature: 9ºC or higher
2
Defrosting operation has continued for 10 minutes.
Speed 9
Speed 5
Speed 3
Speed 3
OFF
34
30
25
40
34
30
43
37
30
Auto fan control,
or the set fan speed
<SRK20HG>
<SRK28HG>
<SRK40HG>
Indoor unit fan
Outdoor unit fan
Compressor
Speed 9 fixed
ON
ON
(b)
When the compressor and outdoor fan are stopped
1) While the compressor operation is delayed.
2) Up until 5 minutes have passed
since the end of a compressor
start delay operation, when 52C
goes OFF, the indoor unit’s fan
speed changes forcibly from
OFF to speed 1.
Indoor heat exchanger temp. (˚C)
Notes (1) Room temperature is not adjusted during the HIGH POWER operation.
(2) Protective function will actuate with prioriy even during the HIGH POWER
operation.