5
-
2.2 Range of usage & limitations
Indoor return air temperature
(Upper, lower limits)
Refrigerant line (one way) length
Max. 15m
All models
Power source voltage
Rating
±
10%
Voltage at starting
Min. 85% of rating
Frequency of ON-OFF cycle
ON and OFF interval
Max. 3 minutes
Outdoor air temperature
(Upper, lower limits)
Vertical height difference between
outdoor unit and indoor unit
Max. 5m (Outdoor unit is higher)
Max. 5m (Outdoor unit is lower)
Item
Models
Max. 10 times/h
(Inching prevention 3 minutes)
Cooling operation : Approximately 21 to 32˚C
Heating operation : Approximately 15 to 30˚C
Cooling operation : Approximately 21 to 43˚C
Heating operation : Approximately - 5 to 21˚C