8
-
(2) Range of usage & limitations
(3) Exterior dimensions
(a)
Indoor unit
Models SRK20ZD-S1, 25ZD-S1, 35ZD-S1, 50ZD-S1
Indoor return air temperature
(Upper, lower limits)
Refrigerant line (one way) length
Max. 15m
SRK20ZD-S1, 25ZD-S1, 35ZD-S1
SRK50ZD-S1
Cooling operation : Approximately 21 to 32˚C
Heating operation : Approximately 15 to 30˚C
Cooling operation : Approximately 21 to 43˚C
Heating operation : Approximately -5 to 21˚C
Power source voltage
Rating
±
10%
Voltage at starting
Min. 85% of rating
Frequency of ON-OFF cycle
Max. 7 times/h
(Inching prevention 5 minutes)
Max. 4 times/h
(Inching prevention 10 minutes)
ON and OFF interval
Max. 3 minutes
Outdoor air temperature
(Upper, lower limits)
Vertical height difference between
outdoor unit and indoor unit
Max. 10m (Outdoor unit is higher)
Max. 10m (Outdoor unit is lower)
Max. 25m
Max. 15m (Outdoor unit is higher)
Max. 15m (Outdoor unit is lower)
Item
Models
VIEW A
117.5
580
117.5
148.5
216.5
216.5
8.2
44.5
236.1
5.7
450
450
67.5
42.7
47.2
175
44.5
216.5
216.5
148.5
53.5
Piping for Gas
Drain hose 540 (ø16)
Piping for Liquid 465.1 (ø6.35)
Piping hole (ø65)
Piping hole (ø65)
( )
20,25,35:
ø9.52
50:
ø12.7 397.1
45
14.5
60
788
5
60
45
815
A
250
Unit: mm
Piping hole right(left)
Terminal block
9
60
45
3
249
150
18
56
Remote controller
Summary of Contents for SRK56CE-S1
Page 138: ... 136 MEMO ...
Page 262: ... 260 MEMO ...