121
-
2
Stop data
Remote control setting
Fan speed
switching
Operation
switching
Displayed data
Temperature
setting
21
°
C
22
°
C
23
°
C
24
°
C
25
°
C
26
°
C
27
°
C
28
°
C
29
°
C
30
°
C
Displays the reason for the stop (stop code) the previous time when the air conditioner was stopped by protective stop control.
Displays the reason for the stop (stop code) 2 times previous when the air conditioner was stopped by protective stop control.
Displays the reason for the stop (stop code) 3 times previous when the air conditioner was stopped by protective stop control.
Displays the reason for the stop (stop code) 4 times previous when the air conditioner was stopped by protective stop control.
Displays the reason for the stop (stop code) 5 times previous when the air conditioner was stopped by protective stop control.
Displays the reason for the stop (stop code) 6 times previous when the air conditioner was stopped by protective stop control.
Displays the reason for the stop (stop code) 7 times previous when the air conditioner was stopped by protective stop control.
Displays the reason for the stop (stop code) 8 times previous when the air conditioner was stopped by protective stop control.
Displays the reason for the stop (stop code) 9 times previous when the air conditioner was stopped by protective stop control.
Displays the reason for the stop (stop code) 10 times previous when the air conditioner was stopped by protective stop control.
Cooling
LO
(iii) Error code, stop code table
(Assignment of error codes and stop codes is done in common for all models.)
(2 times)
(3 times)
OFF
OFF
Major category
Number of flashes
when in service mode
Minor category
Error content
Stop code
or
Error code
TIMER
light
(1’s digit)
RUN
light
(10’s digit)
Cause
Occurrence conditions
Error
display
Auto
recovery
1 time
flash
1 time
flash
2 time
flash
1 time
flash
3 time
flash
1 time
flash
2 time
flash
2 time
flash
3 time
flash
3 time
flash
4 time
flash
5 time
flash
6 time
flash
7 time
flash
9 time
flash
7 time
flash
2 time
flash
3 time
flash
4 time
flash
5 time
flash
6 time
flash
0
Normal
Current
Cut
Outdoor
unit
error
Outdoor
fan motor
error
Current
safe
11
21
31
32
33
34
35
36
37
22
23
29
27
12
13
14
15
16
Compressor Software Start Compressor lock
Compressor wiring short circuit
Compressor output is open phase
Outdoor unit s circuit board is faulty
Compressor start fails 42 times in succession and the
reason for the final failure is current cut.
After the compressor starts, it stops due to current cut at
less than 20 rps.
When operation is stopped by current cut at 20 rps or
higher.
When the DC voltage (DC 280 V) exceeds 350 V.
When it is judged that the power transistor was damaged
at the time the compressor started.
When it is judged that the power transistor was damaged
at the time the compressor started.
When PWM calculation results of 0% continue for 3
minutes or longer.
When PWM calculation results of 90% and an input current
lower than the set value continue for 3 minutes or longer.
When an abnormal stop occurs 3 times with automatic
recovery within 20 minutes after the outdoor unit s power
supply was turned on.
When the power supply voltage drops during operation.
When a fan speed of 75 rpm or lower continues for 30
seconds or longer.
When there is a current safe stop in current safe I mode
during cooling operation.
When there is a current safe stop in current safe I mode
during heating operation.
When there is a current safe stop in current safe II mode
during cooling operation.
When there is a current safe stop in current safe II mode
during heating operation.
When there is a current safe stop in current safe III mode
during cooling operation.
When there is a current safe stop in current safe III mode
during heating operation.
When there is a current safe stop in current safe III + 3A
mode during heating operation.
Lower than 20 rps
20 rps or higher
Excessive voltage
(DC 350 V)
Short circuit in the power
transistor (high side)
Current cut circuit
breakdown
PWM calculation results
are abnormal.
Input is 2A or lower
(PWM 90% or higher)
Abnormal stop 3 times in
20 minutes.
Voltage drop
Outdoor unit s fan motor
is abnormal
Cooling current safe I
Heating current safe I
Cooling current safe II
Heating current safe II
Cooling current safe III
Heating current safe III
Heating current safe
III + 3A
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Service valve closed
Compressor output is open phase.
Electronic expansion valve is faulty.
Service valve is closed.
Compressor output is open phase.
Compressor is faulty.
Electronic expansion valve is faulty.
Service valve is closed.
Compressor output is open phase.
Electronic expansion valve is faulty.
Refrigerant is insufficient.
Outdoor fan motor is faulty.
Connector connections are poor.
Outdoor unit s circuit board is faulty.
Overcharge
Compressor lock
Overcharge
Compressor lock
Overcharge
Compressor lock
Overcharge
Compressor lock
Overcharge
Compressor lock
Overcharge
Compressor lock
Overcharge
Compressor lock
Power supply construction is defective.
Outdoor unit s circuit board is faulty.
Compressor wiring is disconnected.
Outdoor unit s circuit board is faulty.
Compressor wiring is disconnected.
Power transistor is damaged.
Outdoor unit s circuit board is faulty.
Power transistor is damaged.
Outdoor unit s circuit board is faulty.
Power transistor is damaged.
Outdoor unit s circuit board is defective.
Power supply is abnormal.