173
-
Serial signal transmission error
[Wiring error including power cable, defective indoor/
outdoor unit PCB]
Does error persist after power
reset?
Is there any wrong connection on
indoor/outdoor unit wiring?
Is DC 0~Approx. 12V detected
between
2
~
3
terminals on
indoor unit terminal block?
YES
YES
NO
NO
YES
NO
Trouble by transient cause, not unit trouble.
Correct improper wire connection on indoor/
outdoor unit.
Defective indoor unit PCB
YES
YES
NO
NO
Is DC 0~Approx. 12V detected
between
2
~
3
terminals on
outdoor unit terminal block?
Is AC 220/230/240V applied
between
1
~
2
on the outdoor side
terminal block?
Defective indoor unit PCB. Check crossover wires.
Defective outdoor unit PCB
Check crossover wires.
(d)
Phenomenon observed after shortcircuit, wire breakage on sensor.
(i)
Indoor unit
Phenomenon
Sensor
Shortcircuit
Broken wire
Cooling
Release of continuous compressor operation command
Heating
Continuous compressor operation command is not released.
Cooling
System can be operated normally.
Heating
High pressure control mode
(ii)
Outdoor unit
Phenomenon
Sensor
Shortcircuit
Broken wire
Cooling
System can be operated normally.
Heating
Defrosting is not performed.
Cooling
System can be operated normally.
Heating
Defrosting is not operated.
All modes
Operation
mode
Room temperature
sensor
Continuous compressor operation command is not released.
Release of continuous compressor operation command
Continuous compressor operation command is not released.
(Anti-frosting)
Hot keep (Indoor fan stop)
Heat exchanger
sensor
Operation
mode
System can be operated normally.
Defrosting is performed for 10 minutes at approx. 1 hour.
System can be operated normally.
Defrosting is performed for 10 minutes at intervals of approx. 1 hour.
Compressor stop
Heat exchanger
sensor
Outdoor temperature
sensor
Discharge pipe
sensor
Compressor overload protection is disabled.
(Can be operated.)