229
-
D Block
C Block
B Block
A Block
(10) Outline of dehumidifying operation
(a)
Choose the appropriate operation block area by the difference between room temperature and thermostat
setting temperature as shown below.
¡
Operation block area
–2
0
+3
Room temp.
– Setting temp.(deg)
(b)
Start up operation
Compressor
and
outdoor fan
ON
OFF
OFF
Indoor fan
Start
Temperature check
Speed 4
3
6
9
12
0
Speed 1
20
seconds
minutes
C.D Block
Compressor
and
outdoor fan
ON
OFF
OFF
Indoor fan
Start
Temperature check
Speed 4
12
0
minutes
A.B Block
Operation block decision
Note (1) Thermostat operation is performed in A, B Block. When compressor and indoor fan stop by thermostat operation within 12 minutes from start, temperature
check is performed by operating indoor fan at speed 1 for 20 seconds before finishing 12 minutes and allowing decision of next operation block.
(c)
Thermostat operation
The compressor and outdoor fan and turned on and off as shown below according to the temperature setting.
(d)
HIGH POWER operation ( “HI POWER” button on the remote control : ON)
The following operation is performed for 15 minutes without relation to the set temperature or fan speed setting.
(e)
ECONOMY operation ( “ECONO” button on the remote control : ON)
The set temperature changes as shown at right, and the
indoor unit fan speed is set on speed 4.
Notes (1) Room temperature is not adjusted during the HIGH POWER operation.
(2) Protective functions will actuate with priority even during the HIGH POWER op-
eration.
OFF
ON
Set temp.
-1
Room temp.
Compressor
Outdoor fan
Indoor unit fan
Outdoor unit fan
Compressor
Speed 9 fixed
ON
ON
Running time
Running start ~ 1 hour
1~2 hours
2 hours ~
Set temperature compensation
Set tempe0.5
Set tempe1.0
Set tempe1.5