231
-
(b)
Within 30 minutes after either auto or manual operation stops, if auto operation is started, or if you switch to auto operation during
manual operation, the system runs in the previous operation mode.
(c)
The temperature is checked 1 time in 30 minutes after the start of operation, and if the judgment differs from the previous operation
mode, the operation mode changes.
(d)
Setting temperature can be adjusted within the following range. There is the relationship as shown below between the signals of
the wireless remote control and the setting temperature.
Signals of wireless remote control (Display)
–6
–5
–4
–3
–2
–1
±
0
+1
+2
+3
+4
+5
+6
Setting
Cooling
18
19
20
21
22
23
24
25
26
27
28
29
30
temperature
Dehumidifying
18
19
20
21
22
23
24
25
26
27
28
29
30
Heating
20
21
22
23
24
25
26
27
28
29
30
31
32
(12) Outline of fan operation (Cooling only type only)
(a)
Operation of major functional components
(b)
HIGH POWER operation (“HI POWER” button on the remote control : ON)
The following operation is performed for 15 minutes without relation to the set temperature or fan speed setting.
52C
Indoor fan motor
Outdoor fan motor
Flap and louver
Speed 9
Speed 8
Speed 8
OFF
OFF
Depend on the flap and louver control
Speed 6
Speed 4
Speed 2
High power
AUTO
HIGH
MED
LOW
ECONO
Functional
components
Fan speed switching
Indoor unit fan
Outdoor unit fan
Compressor
Speed 9 fixed
OFF
OFF
Note (1) Protective functions will actuate with priority even during the HIGH POWER operation.
(13) Regulation of outdoor air flow
The fan operates as follows according to the outdoor air temperature. (Except during defrost.)
S
SRK63 HE-S1, 63CE-S1
Cooling, thermaldry
Heating
Outdoor air temp. (˚C)
32
2nd speed
1st speed
30
Outdoor air temp. (˚C)
12
2nd speed
1st speed
10
S
SRK71 HE-S1, 71CE-S1
Cooling, thermaldry
Heating
Outdoor air temp. (˚C)
25
2nd speed
1st speed
23
3rd speed
32
30
Outdoor air temp. (˚C)
12
2nd speed
1st speed
10
3rd speed
18