26
-
(p) Heating low outdoor temperature protective control (50 type only)
◆
<
I
>
(a)
Operating conditions:
When the outdoor air temperature sensor (Th5) is 4ºC or lower continues for 5 minutes while the
outdoor speed is other than 0 rps.
(b)
Operation content:
When the command speed is less than 22 rps, the command speed is forcibly set at 22 rps.
(c)
Reset conditions:
When the outdoor air temperature sensor (Th5) becomes 6ºC or higher.
◆
<
II
>
(a)
Operating conditions:
When the outdoor air temperature sensor (Th5) is 0ºC or lower continuously for 5 minutes while
the outdoor speed is other than 0 rps.
(b)
Operation content:
The outdoor fan motor speed is raised to the next higher speed. (Upper limit 2nd speed)
(c)
Reset conditions:
When the outdoor air temperature sensor (Th5) becomes 2ºC or higher.
◆
<
III
>
(a)
Operating conditions:
When the temperature sensed by the outdoor heat exchanger sensor (Th4) becomes –10ºC or
lower continuously for 1 minute.
(b)
Operation content:
When the command speed upper limit is set at 70 rps.
(c)
Reset conditions:
When the temperature sensed by the outdoor heat exchanger sensor (Th4) becomes -7ºC or higher.
(q) Stop mode
(i)
Operating conditions:
When the operation mode is changed, when the dehumidifying operation is changed from the
heating oriented mode to the cooling oriented mode or vice versa, or when the inverter speed turns to 0 rps. [When 0 rps is
commanded from the indoor unit controller, or when an outdoor protective function is actuated]
(ii)
Detail of operation
◆
20, 25, 35 type
When stopped by indoor unit controller
When stopped or reset by outdoor unit protective function
Function
Operation
Heating, heating
Cooling, cooling
Heating, heating
Cooling, cooling
oriented dehumidifying
oriented dehumidifying
oriented dehumidifying
oriented dehumidifying
Stop
Full stop
Stop
Full stop
Stop
Restart
Stop
Restart
(0 rps command)
(0 rps command)
(0 rps command)
(0 rps command)
Inverter
speed
Indoor
fan
Indoor
power
relay
Outdoor
fan
4-way
valve
(Command
speed)
0
(Speed
dependent)
OFF
ON
OFF
3 min.
(1)
3 min.
(1)
2 min.
2 min.
55 sec.
55 sec.
Hot keep
2 min.55sec.
ON
OFF
ON
OFF
1st speed