48
-
Outdoor unit error
[Broken power transistor
broken compressor wire]
Compressor overheat
[Gas shortage, defective discharge
pipe sensor]
Is output voltage applied to all 3
phases of power transistor?
(Refer to page 53 for details)
Defective inverter
Is compressor wiring connected
securely?
Connect securely.
Inspect compressor.
YES
YES
NO
NO
Is Discharge pipe sensor
resistance value good?
(Page 47)
Is sufficient quantity of refrigerant
circulated?
Defective inverter
YES
YES
NO
NO
YES
NO
Gas shortage
Connector connection check, resistance
value check, replacement of discharge pipe
sensor
Does trouble persist after
charging gas?
Clogged capillary tube,
etc.