56
-
'13 • SRK-T-144
Indoor heat exchanger
temperature (ºC)
2.5
5
8
0 rps
Lower
limit
speed
compressor
command
speed
Indoor heat exchanger temperature
(b) Frost prevention control
(During cooling or dehumidifying)
(i) Operating conditions
1) Indoor heat exchanger temperature (Th2) is lower than 5ºC.
2) 5 minutes after reaching the compressor command speed except 0 rps.
(ii) Detail of anti-frost operation
(iii) Reset conditions:
When either of the following condition is satisfied.
1) The indoor heat exchanger temperature (Th2) is 8ºC or higher.
2) The compressor command speed is 0 rps.
(c) Cooling overload protective control
(i) Operating conditions:
When the outdoor air temperature (TH2) has become continuously for 30 seconds at 41ºC
or more, or 47ºC or more with the compressor running, the lower limit speed of compressor
is brought up.
(ii) Detail of operation
1) The outdoor fan is stepped up by 3 speed step. (Upper limit 7th speed.) (model SRK20~35 only)
2)
The lower limit of compressor command speed is set to 30 or 40 rps and even if the calculated result becomes lower than
that after fuzzy calculation, the speed is kept to 30 or 40 rps. However, when the thermo OFF, the speed is reduced to 0 rps.
(iii) Reset conditions:
When either of the following condition is satisfied.
1) The outdoor air temperature is lower than 40ºC.
2) The compressor command speed is 0 rps.
Notes (1) When the indoor heat exchanger temperature is in the range of 2.5~5ºC, the speed is reduced by 4 rps at each 20 seconds.
(2) When the temperature is lower than 2.5ºC, the compressor is stopped.
(3) When the indoor heat exchanger temperature is in the range of 5~8ºC, the compressor command speed is been maintained.
Item
5°C or lower
2.5°C or lower
Lower limit of compressor command speed
22 rps (model SRK50, 60 : 25 rps)
0 rps
Indoor fan
Depends on operation mode
Protects the fan tap just before
frost prevention control
Outdoor fan
Depends on command speed
Depends on stop mode
4-way valve
OFF
Item
SRK20~60
Outdoor air temperature
41°C or more
47°C or more
Lower limit speed
30 rps
40 rps
Model
Outdoor air temperature (ºC)
10
1((
10
40 41
46 47