'13 • SRK-T-144
(d) Cooling high pressure control
(i) Purpose:
Prevents anomalous high pressure operation during cooling.
(ii) Detector:
Outdoor heat exchanger sensor (TH1)
(iii) Detail of operation:
A
B
C
Outdoor heat exchanger temperature (°C)
6 (8) rps
(1)
6 (8) rps
(1)
0rps
After lapse of 30 (20) sec. or over
(3)
After lapse of 30 (20) sec. or over
(3)
After lapse of 30 (20) sec. or over
(3)
lower limit
speed 30 rps
(Example) Fuzzy
Notes (1) When the outdoor heat exchanger temperature is in the range of A~Cº C, the speed is reduced by 6 (8) rps at each 30 (20) seconds.
(2) When the temperature is C ºC or higher, the compressor is stopped.
(3) When the outdoor heat exchanger temperature is in the range of A~C ºC, if the compressor command speed is been maintained and the operation has
continued for more than 30 (20) seconds at the same speed, it returns to the normal cooling operation.
(4) Value in ( ) are for the model SRK50, 60.
(e) Cooling low outdoor temperature protective control
(i) Operating conditions:
When the outdoor air temperature (TH2) is 22ºC or lower continues for 20 seconds while
the compressor command speed is other than 0 rps.
(ii) Detail of operation:
1)
The lower limit of the compressor command speed is set to 44 (30) <45 (35) > rps and even if the speed be
-
comes lower than 44 (30) < 45(35) > rps, the speed is kept to 44 (30) <45 (35) > rps. However, when the thermo
OFF, the speed is reduced to 0 rps.
2)
The upper limit of the compressor command speed is set to 50 (60) <60 (75) > rps and even if the calculated re
-
sult becomes higher than that after fuzzy calculation, the speed is kept to 50 (60) <60 (75) > rps.
Notes (1) Value in ( ) are for outdoor air temperature is C or D
(2) Value in < > are for the model SRK50, 60.
Upper limit 50 <60> rps
Lower limit 44 <45> rps
Upper limit 60 <75> rps
Lower limit 30 <35> rps
C
D
A
B
OFF
ON
ON
Outdoor air temperature (°C)
First time
Since the seconds
times
0 <9>
A
Outdoor air temp. (˚C)
B
C
D
3 <11>
22
25
7 <16>
10 <19>
25
28
¡
Values of A, B, C, D
(iii) Reset conditions:
When either of the following condition is satisfied
1) The outdoor air temperature (TH2) is D ºC or higher.
2) The compressor command speed is 0 rps.
A
B
C
Outdoor heat exchanger
temperature (ºC)
53
58
63
Model SRK20~35
A
B
C
Outdoor heat exchanger
temperature (ºC)
TH2 >= 32ºC
53
58
63
TH2 < 32ºC
51
53
56
Model SRK50, 60
TH2 : Outdoor air temperature