(iv) Press the ON/OFF button.
The air-conditioner's installation location is set.
Press within 60 seconds of setting the installation location (while the installation location setting display illuminates).
(a) Operation of major functional components in heating mode
(b) Details of control at each operation mode (pattern)
(i) Fuzzy operation
Deviation between the indoor temperature setting correction temperature and the return air temperature is calculated in
accordance with the fuzzy rule, and used for control of the air capacity and the compressor speed.
When the defrosting, protection device, etc. is actuated, operation is performed in the corresponding mode.
(ii) Hot keep operation
If the hot keep operation is selected during the heating operation, the indoor blower is controlled based on the tem-
perature of the indoor heat exchanger (Th2) to prevent blowing of cool wind.
However, if the fan speed setting is HI and room temperature is 19
ºC or higher, this control is not executed.
ON
OFF
ON
ON
ON
OFF
(few minutes ON)
ON
ON(HOT KEEP)
OFF
OFF
(3 minutes ON)
OFF
OFF
Thermostat ON
Thermostat OFF
Failure
Heating
Compressor
Indoor fan motor
Outdoor fan motor
4-way valve
12~106rps
12~106rps
12~74rps
12~42rps
SRK50ZMX-S
30~115rps
30~115rps
30~76rps
30~46rps
SRK35ZMX-S
30~102rps
30~102rps
30~72rps
30~42rps
SRK25ZMX-S
30~94rps
30~94rps
30~66rps
30~40rps
SRK20ZMX-S
Model
Fan speed
12~120rps
12~120rps
12~90rps
12~58rps
SRK60ZMX-S
Auto
MED
HI
LO
12~40rps
30~40rps
30~40rps
30~40rps
12~40rps
ULO
(c) Defrosting operation
(i) Starting conditions (Defrosting operation can be started only when all of the following conditions are met.)
1) After start of heating operation
When it elapsed 45 (model SRK50, 60 : 35) minutes. (Accumulated compressor operation time)
2) After end of defrosting operation
When it elapsed 45 (model SRK50, 60 : 35) minutes. (Accumulated compressor operation time)
3) Outdoor heat exchanger sensor (TH1) temperature
When the temperature has been below
-
5ºC for 3 minutes continuously.
(14) Outline of heating operation