'17 • SCM-T-225
Error code
Remote control:
LED
Green
Red
Content
Indoor Keeps flashing Stays OFF
E58
Current safe stop
Outdoor
–
3
-
time flash
Error code
Remote controller: E58
LED
Green
Red
Indoor
Outdoor
―
Content
Current safe stop
(Model SRC40 - 60)
Keeps flashing Stays Off
3 time flash
1. Applicable model
5. Troubleshooting
All models
When the current safe control
has operated at the compressor
speed of 30 rps or under:
Same as above
• Excessive refrigerant amount
• Indoor,outdoor unit installation
spaces
• Faulty compressor
• Defective outdor air temp.
sensor
• Defective outdoor main PCB
Diagnosis
Countermeasure
2. Error detection method
3. Condition of error displayed
4. Presumable cause
Note:
Is outdoor
ventilation condition
good ?
Inspect
outdor air temperature
sensor.
Is the refrigerant
amount nomal ?
Adjust the refrigerant
amount properly.
Secure space for inlet and
outlet.
Replace compressor.
Replace sensor.
Defective outdoor main
PCB
→
Replace.
(Defective outdor air temp.
sensor input circuit)
Inspect
compressor.
YES
YES
YES
NO
NO
NO
NO
NO