288
-
Compressor (CM)
10. Loosen a nut and remove
the terminal cover.
11. Disconnect the fasten
connectors from compressor.
U: Red cable
V: White cable
W: Black cable
Note : Be sure to do above
work after elapsing
3 minutes from power
OFF.
12. Disconnect the pipes for
suction and discharge by
brazing.
(It is available to cut suction
and discharger pipes to
remove the compressor)
When brazing, do not forget
to disconnect suction pipe
temperature sensor (Tho-S)
and discharge pipe
temperature sensor (Tho-D)
from sockets.
Without disconnecting sensors,
sensors may have damage by
the heat during brazing.
Nut
Terminal cover
U: Red cable V: White cable
W: Black cable
Discharge pipe
Suction pipe
Discharge pipe temperature
sensor (Tho-D)
Suction pipe temperature
sensor (Tho-S)
Position to be
disconnected
Position to be
disconnected
Accumulator
Compressor
〈
Caution
〉
'17 • SCM-T-225