-
39
-
'17 • SCM-T-225
Adapted to
RoHS directive
Model
Item
FDTC50VF
Panel
TC-PSA-25W-E
Power source
1 Phase, 220−240V, 50Hz
Operation data
Cooling
Heating
Nominal capacity (1)
kW
5.0
5.8
Sound power level
dB(A)
Cooling : 60
Heating : 60
Sound pressure level
Cooling P-Hi : 47 Hi : 42 Me : 36 Lo : 30
Heating P-Hi : 47 Hi : 42 Me : 36 Lo : 32
Exterior dimensions
Height x Width x Depth
mm
Unit 248 × 570 × 570
Panel 35 × 700 × 700
Exterior appearance
(Munsell color)
Plaster white
(6.8Y8.9/0.2) near equivalent
Net weight
kg
UNIT 15 PANEL 3.5
Heat exchanger
Louver fin & inner grooved tubing
Air handling equipment
Fan type & Q'ty
Turbo fan × 1
Motor <Starting method>
W
33 < Direct line start >
Air flow (Standard)
m
3
/min
Cooling P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 7
Heating P-Hi : 13.5 Hi : 11.5 Me : 9 Lo : 8
Available external static pressure
Pa
0
Outdoor air intake
Not possible
Air filter, Q'ty
Pocket plastic net × 1 (Washable)
Shock & vibration absorber
Rubber sleeve (for fan motor)
Insulation (Noise & heat)
Polyurethane form
Remote control
Wired : RC-EX3, RC-E5, RCH-E3 (option) Wireless : RCN-TC-24W-E2 (option)
Room temperature control
Thermostat by electronics
Safety equipment
Overload protection for fan motor
Frost protection thermostat
Installation data
Refrigerant piping size
mm
Liquid line :
φ
6.35 (1/4")
Gas line :
φ
12.7 (1/2")
Connecting method
Flare piping
Drain pump
Built-in Drain pump
Drain
Hose connectable with VP20
Insulation for piping
Necessary (both Liquid & Gas lines)
IP number
IPX0
Standard accessories
Mounting kit, Drain hose
Notes (1) The data are measured at the following conditions.
The pipe length is 7.5m.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO5151-T1
Heating
20˚C
−
7˚C
6˚C
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation
these values are somewhat higher due to ambient temperature.
(4) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(5) When wireless remote control is used, fan is 3 speed setting(Hi-Me-Lo) only.
H
PJA003Z401