'17 • SCM-T-225
1.2 Exterior dimensions
Models SCM71ZM-S1, 80ZM-S1
RWC000Z302
15
60
380
19
418
73
880
150
580
150
26
340
2-R7.5
223
47.5
310
61
61
110.4
52
185
10
24
750
214.4
52
318.4
52
422.4
52
20
355
170
560
Unit:mm
The height of a wall is 1200mm or less
Notes
(
1
)
It must not be surrounded by walls on four sides.
(
2
)
The unit must be fixed with anchor bolts.
An anchor bolt
must not protrude more than 15mm.
(
3
)
Where the unit is subjected to strong winds, lay it in such a direction that the blower outlet faces perpendicularly to the dominant wind direction.
(
4
)
Leave 1.2m or more space above the unit.
(
5
)
A wall in front of the blower outlet must not exceed the unit's height.
(
6
)
The model name label is attached on the rear panel.
D
Terminal block
C
E
Symbol
Content
A
Service valve connection
(
gas side
)
φ
9.52
(
3
/
8"
)(
Flare
)
B
Service valve connection
(
liquid side
)
φ
6.35
(
1
/
4"
)(
Flare
)
C
Pipe
/
cable draw-out hole
D
Drain discharge hole
φ
20 x 3 places
E
Anchor bolt hole
M10 x 4 places
B
A
Air intake
Air intake
Air outlet
(
Service space for electrical parts
)
Minimum installation space
L2
L4
L1
L3
Center of gravity
Center of gravity
L2
L3
L4
L1
300
100
250
Open
I
II
Open
250
100
500
III
Open
250
150
250
Examples of
Dimensions
installation