27
-
'17 • SCM-T-225
Model
Item
SRF25ZMX-S
Power source
1 Phase, 220−240 V, 50Hz
Operation data
Nominal cooling capacity (range) kW
2.5
Nominal heating capacity (range)
kW
3.4
Sound power level
Cooling
dB(A)
51
Heating
51
Sound pressure level
Cooling
Hi: 40 Me: 32 Lo: 29 ULo: 26
Heating
Hi: 40 Me: 35 Lo: 33 ULo: 28
Silent mode sound pressure level
—
Exterior dimensions (Height x Width x Depth)
mm
600 x 860 x 238
Exterior appearance
( Munsell color )
Fine snow
( 8.0Y 9.3/0.1 ) near equivalent
Net weight
kg
18
Heat exchanger
Louver fins & inner grooved tubing
Fan type & Q'ty
Turbo fan x 1
Fan motor (Starting method)
W
40 x1 (Direct drive)
Air flow
Cooling
m
3
/min
Hi: 9.0 Me: 7.6 Lo: 6.7 ULo: 5.8
Heating
Hi: 10.5 Me: 8.2 Lo: 7.7 ULo: 6.6
Available external static pressure
Pa
0
Outside air intake
Not possible
Air filter, Quality / Quantity
Polypropylene net ( washable ) x 1
Shock & vibration absorber
Rubber sleeve (for fan motor)
Operation control
Remote control
Wireless remote control
Room temperature control
Microcomputer thermostat
Operation display
RUN: Green, TIMER: Yellow, HI POWER: Green, Air outlet selection: Green, ECONO: Green
Safety equipments
Frost protection, Serial signal error protection, Indoor fan motor error protection
Installation data
Refrigerant piping size ( O.D )
mm
Liquid line:
φ
6.35 ( 1/4" ) Gas line:
φ
9.52 ( 3/8" )
Connecting method
Flare connection
Attached length of piping
m
—
Insulation for piping
Necessary (Both sides), independent
Drain hose
Hose connectable ( VP16 )
Drain pump, max lift height
mm
—
Interconnecting wires
Size x Core number
1.5mm
2
x 4 cores ( Including earth cable ) / Terminal block ( Screw fixing type )
IP number
IPX0
Standard accessories
Mounting kit, Clean filter ( Natural enzyme filter x 1, Photocatalytic washable deodorizing filter x 1 )
Option parts
Interface kit ( SC-BIKN2-E )
Notes (1) The data are measured at the following conditions.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO5151-T1
Heating
20˚C
—
7˚C
6˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher
due to ambient conditions.
The pipe length is 7.5m.
Adapted to
RoHS directive
(2) Floor standing type (SRF)
B
RWB000Z056