-
141
-
'19 • SCM-SM-276
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
E37
Outdoor heat exchanger
temperature sensor anomaly
Keeps flashing
Stays OFF
–
8
-
time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
outdoor heat
exchanger temperature
sensor connector
connected
properly?
YES
Are the
characteristics of
outdoor heat exchanger
temperature
sensor
OK?
NO
For the characteristics of outdoor heat exchanger
temperature sensor, see the following graph.
YES
Temperature-resistance characteristics
Temperature sensor resistance (kΩ
)
Temperature (°C)
15
10
5
0
10
30
40
20
50
5kΩ at 25°C
NO
(Broken wire)
(Short-circuit)
Correct connector.
Defective outdoor heat
exchanger temperature
sensor
➞
Replace.
Defective outdoor
unit main or sub
PCB
➞
Replace.
(Defective outdoor heat
exchanger temperature
sensor input circuit)
2. Error detection method
Detection of anomalously low
temperature (resistance) on
the outdoor heat exchanger
temperature sensor
3. Condition of error displayed
•
When the temperature sensor
detects-55°C or lower for 20
seconds continuously within 2
minutes to 2 minutes 20 seconds
after the compressor ON, the
compressor stops. After 3-minutes
delay, the compressor starts again
automatically, but if this anomalous
temperature is detected 3 times
within 40 minutes.
•
When -55°C or lower is detected for 5
seconds continuously within 20 seconds
after compressor ON.
4. Presumable cause
• Defective outdoor unit main
or sub PCB
• Broken sensor harness or
temperature sensing section
• Disconnected wire connection
(connector)
Note:
Summary of Contents for SRK60ZSX-W
Page 2: ......