75
-
'19 • SCM-SM-276
(ii) Control value
Current safe
①
Current safe
②
Current safe
③
Cooling
Heating
Cooling
Heating
Cooling
Heating
13.0
16.0
10.0
10.0
7.5
7.5
Unit: A
(13) Discharge pipe sensor disconnection protection control
(a) When the compressor command speed is other than 0 rps.
(i) Tho-D(10)
-
Tho-D(0) < 8 °C, and Tho-D(10)
-
Tho-A(10) < 5 °C
The compressor command speed is set on A rps for 5 minutes. After 5 minutes, the compressor command speed is set
on B rps for 5 minutes.
(ii) Tho-D(20)
-
Tho-D(15) < 5 °C
The compressor command speed is set on 0 rps.
Notes (1) Tho-D(X): After compressor operation, the discharge pipe temperature sensor after X minutes.
(2) Tho-A(X): After compressor operation, the outdoor air temperature sensor after X minutes.
(11) Current cut
(a) Purpose
(b) Detail of operation
(12) Outdoor unit failure
(23) Indoor fan motor protection
compressor command
(SRF:150)
300
-
Jumper wire (J1)
Jumper wire (J2)