-
42
-
'19 • SCM-SM-276
(b) Control of input signal
Control of input signal (switch input, timer input) connectors (CnT) are provided on the printed circuit board of indoor unit.
However, when the operation of air-conditioner is under the
“
CENTER
”
mode, the wired remote control by CnT is invalid.
(16) Hot keep operation
If the hot keep operation is selected during the heating operation, the indoor fan is controlled based on the temperature of
the indoor heat exchanger (Th2) to prevent blowing of cool wind.
However, if the fan speed setting is HI and room temperature is 19°C or higher, this control is not executed.
(17) Frost prevention control
(a) Operating conditions
(b) Detail of anti-frost operation
(c) Reset condition
Indoor heat exchanger
temperature (ºC)
2.5
8
Operation mode
Item
Protective control
Reset
Compressor operation
Indoor fan
Forced outage
Operation instruction
Depends on operation mode
8
2.5
(i)
(ii)
Reset
Protective
control
CnT Input
Unit
(CASE A)
Unit
(CASE B)
OFF
OFF
*ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
Note (1) The ON with the * mark indi-
cates an ON operation using the
wired remote control, etc.
*ON
(i) Level input
If the factory settings (Jumper wire J1 EXTERNAL INPUT on the PCB of indoor unit) are set, or “LEVEL IN-
PUT” is selected in the wired remote control’s indoor unit settings.
1) Input signal to CnT OFF
→
ON Air-conditioner ON
2) Input signal to CnT ON
→
OFF Air-conditioner OFF
(ii) Pulse input
When Jumper wire J1 on the PCB of indoor unit
is cut at the field or “PULSE INPUT” is selected in the wired
remote control’s indoor unit settings.
Input signal to CnT becomes valid at OFF
→
ON only and the motion of air-conditioner [ON/OFF] is inverted.
CnT Input
Unit
(CASE A)
Unit
(CASE B)
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
OFF
(12) Current cut
(a) Purpose:
(b) Detail of operation:
(13) Outdoor unit failure
(18) Indoor fan motor protection
compressor command
300
-
(Model SCM40, 45, 50, 60, 71, 80 only)
min
-1
Summary of Contents for SRK60ZSX-W
Page 2: ......