81
-
'19 • SCM-SM-276
When a heat exchanger temperature sensor 1 wire disconnection is detected
while operation is stopped. (If a temperature of –28ºC or lower is detected
for 15 seconds, it is judged that the wire is disconnected.)
(Not displayed during operation.)
When a room temperature sensor wire disconnection is detected while
operation is stopped. (If a temperature of –45ºC or lower is detected for
15 seconds, it is judged that the wire is disconnected.)
(Not displayed during operation.)
•
Broken heat exchanger temperature
sensor 1 wire, poor connector
connection
• Indoor unit PCB is faulty
-
• Broken room temperature
sensor wire, poor connector
connection
• Indoor
unit
PCB is faulty
Heat exchanger
temperature
sensor 1 error
Room
temperature
sensor error
When conditions for turning the indoor unit’s fan motor on exist during air-
conditioner operation, an indoor unit fan motor speed of 300 min
-1
• Defective fan motor
, poor
connector connection
Indoor fan
motor error
–55ºC or lower is detected for 5 seconds continuously 3 times within
40 minutes after initial detection of this anomalous temperature.
Or –55ºC or higher is detected for within 20 seconds after power ON.
(The compressor is stopped.)
–55ºC or lower is detected for 5 seconds continuously 3 times within
40 minutes after initial detection of this anomalous temperature.
Or –55ºC or higher is detected for within 20 seconds after power ON.
(The compressor is stopped.)
•
Broken heat exchanger temperature
sensor wire, poor connector
connection
• Outdoor unit main PCB is faulty
Outdoor heat
exchanger
temperature
sensor error
–25ºC or lower is detected for 5 seconds continuously 3 times within 40
minutes after initial detection of this anomalous temperature.
(The compressor is stopped.)
•
Broken discharge pipe temperature
sensor wire, poor connector
connection
• Outdoor unit main PCB is faulty
Dischar
ge pipe
temperature
sensor error
The compressor output current exceeds the set value during compressor
start.
(The air-conditioner stops.)
•
,
Compressor locking, open phase
on compressor output, short
circuit on power transistor
service valve is closed
Current cut
Outdoor suction
pipe temperature
sensor error
–55ºC or lower is detected for 5 seconds continuously 3 times within 40
minutes after initial detection of this anomalous temperature.
Or –55ºC or higher is detected for within 20 seconds after power ON.
(The compressor is stopped)
gency stop caused by trouble in the outdoor unit,
When there is an emer
or the input current value is found to be lower than the set value.
(The air-conditioner stops.)
When the power transistor is judged breakdown while compressor
starts.
(The compressor is stopped.)
• Broken compressor wire
• Compressor blockage
Trouble of
outdoor unit
When the value of the discharge pipe temperature sensor exceeds the set
value. (The air-conditioner stops.)
• Gas shortage, defective discharge
pipe temperature sensor, service
valve is closed
Over heat of
compressor
When there is no signal between the indoor unit PCB and outdoor unit
PCB for 10 seconds or longer (when the power is turned on), or when
there is no signal for 7 minute 35 seconds or longer (during operation)
(the compressor is stopped).
• Defective power source
,
Broken signal wire, defective
indoor/outdoor unit sub PCB
Error of signal
transmission
If the compressor motor’s magnetic pole positions cannot be correctly
detected when the compressor starts.
(The air-conditioner stops.)
• Defective compressor
• Open phase on compressor
• Defective outdoor unit PCB
• Service valve is closed.
• Refrigerant is insuf
Outdoor unit sub
PCB communication
error
• Outdoor unit sub PCB fauly
• Poor connection of wire between
outdoor unit sub PCB – main PCB
• Defective
limit switch
• Defective
suction panel set
• Defective indoor unit control PCB
Communication error for 15 minutes: Detected more than 15 seconds
4 times
ficient
Rotor lock
When the outdoor unit’s fan motor speed continues for 30 seconds or
longer at 75 min
-1
or lower. (3 times) (The air-conditioner stops.)
• Defective fan motor
, poor
connector connection
Outdoor fan
motor error
Indoor unit display panel
Models SCM71, 80
Description
of trouble
Cause
Display (flashing) condition
When the compressor command speed is lower than the set value and
the current safe has operated. (the compressor stops)
• Overload operation
• Overchar
ge
• Compressor locking
Current safe
stop
The wired remote control wire Y is open. The wired remote
control wires X and Y
are reversely connected. Noise is penetrating
the wired remote control lines. The wired remote control or indoor
PCB is faulty
. (The communications circuit is faulty.)
• Broken wired remote control
wire, defective indoor unit PCB
Error of wired
remote control
wiring
Limit switch
error
• Broken power transistor
Power
transistor
error
When a heat exchanger temperature sensor 2 wire disconnection is detected
while operation is stopped. (If a temperature of –28ºC or lower is detected
for 15 seconds, it is judged that the wire is disconnected.)
(Not displayed during operation.)
If the float switch OPEN is defected for 3 seconds continuously or if
float switch connector or wire is disconnected.
• Defective drain pump (DM),
broken drain pump wire
•
Anomalous float switch operation
• Defective indoor
unit
PCB faulty
Heat exchanger
temperature
sensor 2 error
Drain
(3)
trouble
When the value of the outdoor heat exchanger temperature sensor
exceeds the set value.
• Overload operation, overchar
ge
• Broken outdoor heat exchange
temperature sensor wire
• Service valve is closed
Cooling high
pressure
protection
When the wrong voltage connected for the power source
.
When the outdoor unit main PCB is faulty
.
• Defective active filter
Active filter
voltage error
When refrigeration cycle system protective control operates.
Actuation of limit switch
Refrigeration
cycle system
protective
control
ON
ON
ON
1-time
flash
5-time
flash
6-time
flash
2-time
flash
7-time
flash
TIMER
light
—
4-time
flash
3-time
flash
2-time
flash
ON
ON
ON
ON
6-time
flash
ON
ON
ON
ON
2-time
flash
ON
RUN
light
—
—
—
—
—
ON
ON
3-time
flash
4-time
flash
ON
5-time
flash
7-time
flash
E 16
E 9
• Broken outdoor air temperature
sensor wire, poor connector
connection
• Outdoor unit main PCB is faulty
Outdoor air
temperature
sensor error
Keeps
flashing
Keeps
flashing
Keeps
flashing
Keeps
flashing
Keeps
flashing
E 38
E 37
E 39
E 53
E 42
E 59
E 36
E 5
E 60
E 47
E 48
E 35
E 1
E 58
E 51
Wired
(2)
remote
control
display
E 57
E 45
—
—
—
(5) Self-diagnosis table
or lower is measured for 30 seconds or longer. (The air conditioner stops.)
(3)SRR series only.
Stays
OFF
Stays
OFF
Stays
OFF
Stays
OFF
Stays
OFF
8-time
flash
8-time
flash
8-time
flash
8-time
flash
5-time
flash
4-time
flash
2-time
flash
1-time
flash
2-time
flash
3-time
flash
1-time
flash
5-time
flash
6-time
flash
ON
2-time
flash
7-time
flash
2-time
flash
2-time
flash
4-time
flash
Outdoor
main PCB
Red LED
Stays
OFF
Stays
OFF
1-time
flash
2-time
flash
1-time
flash
Keeps
flashing
-
-
-
•
Broken heat exchanger temperature
sensor 2 wire, poor connector
connection
• Indoor unit PCB is faulty
•
Broken suction pipe temperature sensor
wire, poor connector connection
• Outdoor unit sub PCB is faulty