115
-
'17 • SRK-T-206
(11) Inspection procedure for blown fuse on the indoor and outdoor PCB
Replace the indoor and outdoor PCB and the fan motor. Check then the operation.
Faulty part, other than
fan motor
( )
YES (Fan motor is faulty.)
YES
YES
YES
NO
NO
NO
Replace the faulty part and the
fuse. Test-run then the unit for
checking.
Is there any damage on the internal circuit
of fan motor?
Check the resistance value to judge.
(See pages 113 to 119.)
Is the fuse blown on the indoor and
outdoor PCB?
Is there any faulty part (fan motor, etc)?
(See pages 112 to 119.)
Replace the fuse on the indoor and
outdoor PCB. When the operation is
checked without connecting the fan
motor connector, does the fuse blow?
Go to the inspection procedure for electric
equipment of indoor and outdoor units
(See pages 112 to 119.)
Replace the fuse, and check the operation.
Replace the fan motor, and check the operation.