(12) Outline of automatic operation
(a) Determination of operation mode
The unit checks the indoor air temperature and the outdoor air temperature, determines the operation mode, and then begins
in the automatic operation.
Heating
Dehumidifying
Cooling
Indoor air temperature (˚C)
Outdoor air temperature (˚C)
A
(b) The unit checks the temperature every hour after the start of operation and, if the result of check is not same as the previous
operation mode, changes the operation mode.
(i) If the setting temperature is changed with the wireless remote control, the operation mode is judged immediately.
(ii) When both the indoor and the outdoor air temperatures are in the range “A”, cooling or heating is switched depending on
the difference between the setting temperature and the indoor air temperature.
(iii) When the operation mode has been judged following the change of setting temperature with the wireless remote control, the
hourly judgment of operation mode is cancelled.
(c) When the unit is started again within one hour after the stop of automatic operation or when the automatic operation is
selected during heating, cooling or dehumidifying operation, the unit is operated in the previous operation mode.
(d) Setting temperature can be adjusted within the following range. There is the relationship as shown below between the signals
of the wireless remote control and the setting temperature.
Signals of wireless remote control (Display)
–6
–5
–4
–3
–2
–1
±
0
+1
+2
+3
+4
+5
+6
Setting
Cooling
18
19
20
21
22
23
24
25
26
27
28
29
30
temperature
Dehumidifying
19
20
21
22
23
24
25
26
27
28
29
30
31
Heating
20
21
22
23
24
25
26
27
28
29
30
31
32
(13) Protection control function
(a) Dew prevention control [Cooling]:Prevents dewing on the indoor unit.
(i) Operating conditions:
When the following conditions have been satisfied for more than 30 minutes after starting
operation
1) Compressor's command speed is 32 rps or higher. (SRK20, 25, 35 only)
2) Detected value of humidity is 68% or higher.
(ii) Contents of operation
1) Air capacity control
Note (1) Ranges A and B are as shown below.
Humidity(%)
68
73
Range A
Range B
Model
Item
SRK20, 25, 35ZSPR-S
SRK45ZSPR-S
LO
Upper limit of compressor's command speed RangeA: 45rps, RangeB: 45rps RangeA: 50rps, RangeB: 34rps
Indoor fan
4th speed
AUTO,
HI,MED
Upper limit of compressor's command speed RangeA: 45rps, RangeB: 45rps RangeA: 50rps, RangeB: 34rps
Indoor fan
Adaptable to compressor's command
speed (Lower limit 4th speed)