85
-
'17 • SRK-T-206
'09•SRK-DB-087D
(b)
(i)
(ii)
(iii)
(c)
(d)
27.5
25.5
18.0
18
30
(15)
ࠉ
Outline of cooling operation
(a)
ࠉ
Operation of major functional components in cooling mode
(b) Detail of control in each mode (Pattern)
1) Fuzzy operation
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
(few minutes ON)
OFF
(few minutes ON)
ON
ON
OFF
Thermostat ON
Thermostat OFF
Failure
Cooling
Compressor
Indoor fan motor
Outdoor fan motor
4-way valve
SRK80ZSPR-S
SRK71ZSPR-S
SRK63ZSPR-S
Model
Fan speed
AUTO
MED
HI
LO
20-98rps
20-98rps
20-64rps
20-46rps
20-26rps
20-76rps
20-76rps
20-56rps
20-40rps
20-26rps
12-106rps
12-106rps
12-68rps
12-50rps
12-32rps
ULO
(17)
ࠉ
Outline of automatic operation
(a) Determination of operation mode
Heating
Dehumidifying
Cooling
Indoor air temperature (˚C)
Outdoor air temperature (˚C)
Signals of wireless remote control (Display)
–6
–5
–4
–3
–2
–1
±
0
+1
+2
+3
+4
+5
+6
Setting
temperature
Cooling
Dehumidifying
Heating
A
When both the indoor and the outdoor air temperatures are in the range “A”, cooling or heating is switched depending on
the difference between the setting temperature and the indoor air temperature.
When the operation mode has been judged following the change of setting temperature with the remote control, the hourly
judgment of operation mode is cancelled.
'09•SRK-DB-087D
(b)
(i)
(ii)
(iii)
(c)
(d)
27.5
25.5
18.0
18
30
(15)
ࠉ
Outline of cooling operation
(a)
ࠉ
Operation of major functional components in cooling mode
(b) Detail of control in each mode (Pattern)
1) Fuzzy operation
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
(few minutes ON)
OFF
(few minutes ON)
ON
ON
OFF
Thermostat ON
Thermostat OFF
Failure
Cooling
Compressor
Indoor fan motor
Outdoor fan motor
4-way valve
SRK80ZSPR-S
SRK71ZSPR-S
SRK63ZSPR-S
Model
Fan speed
AUTO
MED
HI
LO
20-98rps
20-98rps
20-64rps
20-46rps
20-26rps
20-76rps
20-76rps
20-56rps
20-40rps
20-26rps
12-106rps
12-106rps
12-68rps
12-50rps
12-32rps
ULO
(17)
ࠉ
Outline of automatic operation
(a) Determination of operation mode
Heating
Dehumidifying
Cooling
Indoor air temperature (˚C)
Outdoor air temperature (˚C)
Signals of wireless remote control (Display)
–6
–5
–4
–3
–2
–1
±
0
+1
+2
+3
+4
+5
+6
Setting
temperature
Cooling
Dehumidifying
Heating
A
When both the indoor and the outdoor air temperatures are in the range “A”, cooling or heating is switched depending on
the difference between the setting temperature and the indoor air temperature.
When the operation mode has been judged following the change of setting temperature with the remote control, the hourly
judgment of operation mode is cancelled.
'09•SRK-DB-087D
(b)
(i)
(ii)
(iii)
(c)
(d)
27.5
25.5
18.0
18
30
(15)
ࠉ
Outline of cooling operation
(a)
ࠉ
Operation of major functional components in cooling mode
(b) Detail of control in each mode (Pattern)
1) Fuzzy operation
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
(few minutes ON)
OFF
(few minutes ON)
ON
ON
OFF
Thermostat ON
Thermostat OFF
Failure
Cooling
Compressor
Indoor fan motor
Outdoor fan motor
4-way valve
SRK80ZSPR-S
SRK71ZSPR-S
SRK63ZSPR-S
Model
Fan speed
AUTO
MED
HI
LO
20-98rps
20-98rps
20-64rps
20-46rps
20-26rps
20-76rps
20-76rps
20-56rps
20-40rps
20-26rps
12-106rps
12-106rps
12-68rps
12-50rps
12-32rps
ULO
(17)
ࠉ
Outline of automatic operation
(a) Determination of operation mode
Heating
Dehumidifying
Cooling
Indoor air temperature (˚C)
Outdoor air temperature (˚C)
Signals of wireless remote control (Display)
–6
–5
–4
–3
–2
–1
±
0
+1
+2
+3
+4
+5
+6
Setting
temperature
Cooling
Dehumidifying
Heating
A
When both the indoor and the outdoor air temperatures are in the range “A”, cooling or heating is switched depending on
the difference between the setting temperature and the indoor air temperature.
When the operation mode has been judged following the change of setting temperature with the remote control, the hourly
judgment of operation mode is cancelled.
(18) Protection control function
(a) Dew prevention control [Cooling]: Prevents dewing on the indoor unit.
(i) Operating conditions:
When the following conditions have been satisfied for more than 30 minutes after starting operation.
1) Compressor’s command speed is 28 rps or higher.
2) Detected value of humidity is 68% or higher.
17-SRK-T206_063-092.indd 85