87
-
'17 • SRK-T-206
(c) Cooling overload protective control
(i) Operating conditions:Reset conditions:
When the outdoor air temperature (TH2) has become continuously for 30
seconds at 38(41)
℃
or more, with the compressor running, the lower limit
speed of compressor is brought up.
(ii) Detail of operation
The lower limit of compressor command speed is set to 25. 30 or 40 rps and even if the calculated result becomes lower
than that after fuzzy calculation, the speed is kept to 25. 30 or 40 rps. However, when the thermo OFF, the speed is
reduced to 0 rps.
(iii) Reset conditions:
When either of the following condition is satisfied.
1) The doudoor aie temperature is lower than 37(40)
℃
.
2) The compressor command speed is 0 rps.
Item
SRK63ZSPR-S
Outdoor air temperature
Lower limit speed
Model
40(46) 41(47)
37(40) 38(41)
46
47
ON2
OFF
ON3
Outdoor air temperature (°C)
38
℃
or more
25
rps
41
℃
or more
30
rps
47
℃
or more
40
rps
Rang A
Rang B
Model 63
Model 71, 80
48
℃
53
℃
52
℃
58
℃
55
℃
51
℃
53
℃
56
℃
P1
P2
P3
60
℃
Item
SRK71, 80ZSPR-S
Outdoor air temperature
Lower limit speed
Model
41
℃
or more
30
rps
47
℃
or more
40
rps
ON1
Note(1) Values in ( ) are for the models 71, 80.
Notes(1) When the outdoor heat exchanger temperature is in the range of P2
-
P3, the speed is reduced by 8 rps at each 20 seconds.
Notes
(2) When the temperature is P3 or higher, the compressor is stopped.
Notes
(3) When the outdoor heat exchanger temperature is in the range of P1
-
P2, if the compressor command speed is been maintained and the operation has
continued for more than 30 seconds at the same speed, it returns to the normal cooling operation.
(d) Cooling high pressure control
(i) Purpose:
Prevents anomalous high pressure operation during cooling.
(ii) Detector:
Outdoor heat exchanger temperature (TH1)
(iii) Detail of operation:
P1
P2
P3
Outdoor heat exchanger temperature (°C)
8rps
(1)
8rps
(1)
0rps
After lapse of 30 sec. or over
(3)
After lapse of 30 sec. or over
(3)
After lapse of 30 sec. or over
(3)
lower limit
speed 30 rps
(Example) Fuzzy
31
32
Rang A
Rang B
(e) Cooling low outdoor air temperature protective control
(i) Operating conditions:
When the outdoor air temperature (TH2) is 22
℃
or lower continues for 20 seconds while the
compressor command speed is other than 0 rps.
(ii) Detail of operation:
1) The lower limit of the compressor command speed is set to B (D) rps and even if the speed becomes lower than
40 (30) rps, the speed is kept to 40 (30) rps. However, when the thermo OFF, the speed is reduced to 0 rps.
2) The upper limit of the compressor command speed is set to A (C) rps and even if the calculated result becomes
higher than that after fuzzy calculation, the speed is kept to A (C) rps.
22
0
OFF
Upper limit C rps
Lower limit D rps
ON
ON
Upper limit A rps
Lower limit B rps
Outdoor air temperature ( °C)
(iii) Reset conditions:
When either of the following condition is satisfied.
1) The outdoor air temperature (TH2) is 25
℃
or higher.
2) The compressor command speed is 0 rps.
Model 63
Model 71, 80
A
C
Note(1) Values in ( ) are for outdoor air temperature is 0
℃.
3
25
●
Compressor command speed
B
B-1
B-2
D
75
60
35
Cancel
Cancel
45
(Unit : rps)
75
60
30
40
Outdoor air temperature ( °C)
24
26
Rang B-1
Rang B-2
Room temperature ( °C)
17-SRK-T206_063-092.indd 87
2017/01/11 14:49:11