-1
-
'13 • PAC-DB-194
Model FDT90VNPVF
2
Model
Item
FDT90VNPVF2
Indoor unit
FDT100VF2
Outdoor unit
FDC90VNP
Power source
Single phase 220-240V 50Hz / 220V 60Hz
Operation
data
Nominal cooling capacity (range)
kW
9.0 [ 1.9(Min.)~ 9.0(Max.)]
Nominal heating capacity (range)
kW
9.0 [ 1.5(Min.)~ 9.0(Max.)]
Power
Cooling
kW
2.67
consumption
Heating
2.19
Max power consumption
4.19
Running
Cooling
A
11.9 / 12.4
current
Heating
9.9 / 10.3
Inrush current, max current
5, 18.0
Power factor
Cooling
%
97 / 97
Heating
96 / 96
EER
Cooling
3.37
COP
Heating
4.11
Sound power level
Cooling
dB(A)
65
69
Heating
Sound pressure level
Cooling
P-Hi : 51 Hi : 40 Me : 37 Lo : 35
57
Heating
55
Silent mode sound pressure level
—
Cooling:52 / Heating:50
Exterior dimensions (Height × Width × Depth)
mm
Unit 298 × 840 × 840
Panel 35 × 950 × 950
750 x 880(+88) x 340
Exterior appearance
( Munsell color )
Plaster White
( 6.8Y8.9/0.2 )near equivalent
Stucco White
( 4.2Y7.5/1.1 )near equivalent
Net weight
kg
UNIT 27 PANEL 5.5
57
Compressor type & Q'ty
—
RMT5118MDE2 ( Twin Rotary type )×1
Compressor motor (Starting method)
kW
—
Direct line start
Refrigerant oil (Amount, type)
—
0.675 MA68
Refrigerant (Type, amount, pre-charge length)
kg
R410A 2.1kg in outdoor unit (incl. the amount for the piping of : 15m)
Heat exchanger
Louver fin & inner grooved tubing
M shape fin & inner grooved tubing
Refrigerant control
Capillary tubes + Electronic expansion valve
Fan type & Q'ty
Turbo fan ×1
Propeller fan ×1
Fan motor (Starting method)
W
140 < Direct line start >
86 < Direct line start >
Air flow
Cooling
m
3
/min
P-Hi : 37 Hi : 27 Me : 24 Lo : 20
63
Heating
49.5
Available external static pressure
Pa
0
0
Outside air intake
Possible
—
Air filter, Quality / Quantity
Pocket plastic net ×1(Washable)
—
Shock & vibration absorber
Rubber sleeve(for fan motor)
Rubber sleeve (for fan motor & compressor)
Electric heater
W
—
—
Operation
control
Remote control
(option) wired : RC-EX1A , RC-E5 , RCH-E3 wireless : RCN-T-36W-E
Room temperature control
Thermostat by electronics
Operation display
—
Safety equipments
Compressor overheat protection, Overcurrent protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Heating overload protection( High pressure control ), Cooling overload protection
Installation
data
Refrigerant piping size ( O.D. )
mm
Liquid line: I/U
φ
9.52 (3/8") Pipe
φ
6.35(1/4")x0.8 O/U
φ
6.35 (1/4")
Gas line: I/U
φ
15.88 (5/8") Pipe
φ
15.88(5/8")x1.0 O/U
φ
15.88 (5/8")
Connecting method
Flare piping
Flare piping
Attached length of piping
m
—
—
Insulation for piping
Necessary (both Liquid & Gas lines)
Refrigerant line (one way) length
m
Max.30m
Vertical height diff. between O.U. and I.U.
m
Max.20m (Outdoor unit is higher)
Max.20m (Outdoor unit is lower)
Drain hose
Hose Connectable VP25(O.D.32)
Holes size
φ
20 x 5pcs
Drain pump, max lift height
mm
Built-in Drain pump , 700
—
Recommended breaker size
A
—
L.R.A. (Locked rotor ampere)
A
5.0
Interconnecting wires Size × Core number
1.5
㎟
×4 cores
(including earth cable) / Termainal block (Screw fixing type)
IP number
IPX0
IPX4
Standard accessories
Mounting kit, Drain hose
Drain elbow, Drain hole grommet
Option parts
—
Note (1) The data are measured at the following conditions.
The pipe length is 7.5m.
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these value are somewhat higher due to ambient
conditions.
(4) Select the breaker size according to the own national standard.
(5) When wireless remote control is used, fan is 3 speed setting (Hi-Me-Lo) only.
(6) The operation data indicates when the air-conditioner is operated at 230V 50Hz or 220V 60Hz.
Item
Operation
Indoor air temperature
Outdoor air temperature
Standards
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO5151-T1
Heating
20˚C
—
7˚C
6˚C
PJF000Z314
F
#