52
-
'13 • PAC-DB-194
Setting 40Pa
Setting 10Pa
Characteristic FAN(2)
Characteristic FAN(1)
Model FDUM100VF1
, 100VF2
Air flow (m
3
/min)
External static pressure (Pa)
0
10
20
30
40
50
60
70
80
90
100
110
10
14
18
22
26
0
10
20
30
40
50
60
70
80
80Pa
90
100
110
21
22
23
24
25
26
27
External static pressure (Pa)
Range of approvable air flow rate
Air flow (m
3
/min)
20Pa
10Pa(Min.)
Characteristic FAN(2)
Characteristic FAN(1)
Model FDUM71VF1
0
10
20
30
40
50
60
70
80
90
100
16
20
24
28
32
36
40
44
Air flow (m
3
/min)
External static pressure (Pa)
110
Setting 10Pa
Setting 60Pa
Upper limit of E.S.P.
Lower limit of E.S.P.
Setting 100Pa
P-Hi
P-Hi
P-Hi
Lo
Lo
Lo
0
10
20
30
40
50
60
70
80
90
100
110
32 33 34 35 36 37 38 39 40
Air flow (m
3
/min)
External static pressure (Pa)
Range of approvable air flow rate
100Pa (Max.)
90Pa
80Pa
70Pa
60Pa(rated)
50Pa
40Pa
30Pa
20Pa
10Pa(Min.)
P-Hi
P-Hi
P-Hi
Hi
Hi
Hi
Me
Me
Lo
Lo
Lo,Me
Upper limit of E.S.P.
Setting 100Pa
Lower limit of E.S.P.
100Pa (Max.)
70Pa
60Pa
50Pa
40Pa
30Pa
In case actual E.S.P. correspond to setting of E.S.P.
In case actual E.S.P. correspond to setting of E.S.P.
Hi
Hi
Hi
Me
Me
Me
90Pa
・
Characteristic FAN (1) shows air flow vs. External Static Pressure (E.S.P.) range where settings of E.S.P. are maximum E.S.P. (100Pa) ,
rated E.S.P., and minimum E.S.P. (10Pa)
・
Characteristic FAN (2) shows air flow vs. E.S.P curve when set fan tap is set P-Hi with each setting of E.S.P by remote control.
・
External Static Pressure (E.S.P.) can be set by wired remote control.
・
You can set required E.S.P. by wired remote control which calculate it with the set air flow rate and pressure loss of the duct connected.
(2) Duct connected-Low / Middle static pressure type (FDUM)
#