111
-
'19 • PAC-SM-332
E48
1. Applicable model
5. Troubleshooting
Diagnosis
Countermeasure
YES
NO
Does any foreign
material intervene in rotational area
of fan propeller?
NO
Does the
fan rotate smoothly when turned
by hand?
NO
Is DC280V
detected between (CNFAN
➀
(red)-
➃
(blue)) of fan motor
connector?
Is F3 fuse blown?
Is normal state restored?
YES
YES
NO
YES
NO
YES
Power source reset
(2)
Remove foreign material.
Replace fan motor.
If resistance between
➀
(Vm):red -
➃
(GND):blue
is detected 1k
Ω
or lower, it
is faulty.
Check power source
voltage.
Replace faulty fan motor
and outdoor unit control
PCB.
Replace fan motor. (If
anomaly persists after
replacing fan motor, replace
outdoor unit control PCB.)
Malfunction by temporary
noise
2. Error detection method
Detected by rotation speed of
outdoor fan motor
3. Condition of error displayed
When actual rotation speed
of outdoor fan motor (FMo1)
drops to 100min
-1
or lower
for 30 minutes continuously,
the compressor and the
outdoor fan motor stop. After
3-minute delay, it starts again
automatically, but if this
anomaly occurs 5 times within
60 minutes after the initial
detection.
4. Presumable cause
• Defective outdoor unit control
PCB
• Foreign material at rotational
area of fan propeller
• Defective fan motor
• Dust on outdoor unit control
PCB
• Blow fuse
• External noise, surge
Note: When E48 error occurs, in almost cases F3 fuse (2A) on the outdoor unit control PCB is blown. There are a lot of cases that fuse is blown and
E48 occurs due to defective fan motor. And even though only the outdoor unit control PCB ( or fuse) is replaced,, another trouble (*1) could
occur. Therefore when fuse is blown, check whether the fan motor is OK or not.
After confirming the fan motor normal, check by power ON. (Don't power ON without confirming the fan motor normal.)
*1 The error which does not seem to relate E48 may occur like as “
WAIT
”, Stay OFF of LED on outdoor unit control PCB, inverter
communication error (E45) and etc.
Error code
Remote control:
LED
Green
Red
Outdoor control PCB
Outdoor inverter
PCB
1-time flash
Keeps flashing
Indoor control PCB
Stays OFF
Keeps flashing
Content
Keeps flashing
Yellow LED
Outdoor fan motor anomaly