84
-
'19 • PAC-SM-332
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
WAIT
Communication error at
initial operation (3/3)
Keeps flashing
Keeps flashing
Stays OFF
2-time flash
1. Applicable model
5. Troubleshooting
Diagnosis
Countermeasure
NO
YES
NO
YES
YES
NO
YES
NO
Replace the
noise filter.
Method to check for inverter PCB before
replacement of blown power source fuse.
Replace the
inverter PCB.
Replace the reactor.
Replace the electrolytic
capacitor.
NO
Replace the power
source fuse.
YES
Is there a
short-circuit between phases of the
noise filter?
Is there a
short-circuit between phases of inverter PCB
input terminals?
Is there
any crack, burning on the power
transistor module?
Is the reactor OK?
Is the
electrolytic capacitor
OK?
From previous page
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Blown fuse
• Faulty noise filter
• Faulty inverter PCB
• Faulty reactor
• Faulty electrolytic capacitor
Note: