'14 • SR-T-157
Air flow
outdoor
air temp.
indoor air temp
16˚CDB
18˚CDB
20˚CDB
22˚CDB
24˚CDB
Hi
10.0
(m
3
/min)
-15˚CWB
2.61
2.56
2.50
2.45
2.39
-10˚CWB
2.96
2.91
2.87
2.79
2.74
-5˚CWB
3.20
3.16
3.09
3.06
3.01
0˚CWB
3.36
3.31
3.25
3.21
3.17
5˚CWB
4.28
4.23
4.21
4.12
4.07
6˚CWB
4.35
4.30
4.25
4.20
4.15
10˚CWB
4.62
4.58
4.55
4.49
4.44
15˚CWB
5.03
4.99
4.95
4.90
4.85
20˚CWB
5.41
5.36
5.34
5.28
5.23
Model FDTC35VF
Cooling Mode
Model FDTC25VF
Cooling Mode
Air flow
outdoor
air temp.
indoor air temp
16˚CDB
18˚CDB
20˚CDB
22˚CDB
24˚CDB
Hi
9.5
(m
3
/min)
-15˚CWB
2.12
2.08
2.03
1.99
1.94
-10˚CWB
2.40
2.36
2.33
2.27
2.22
-5˚CWB
2.60
2.56
2.51
2.48
2.44
0˚CWB
2.73
2.69
2.64
2.61
2.57
5˚CWB
3.47
3.43
3.42
3.35
3.30
6˚CWB
3.53
3.49
3.45
3.41
3.36
10˚CWB
3.75
3.72
3.69
3.64
3.61
15˚CWB
4.08
4.05
4.02
3.97
3.94
20˚CWB
4.39
4.35
4.33
4.28
4.25
Air flow
Outdoor
air temp.
Indoor air temp
21˚CDB
23˚CDB
26˚CDB
27˚CDB
28˚CDB
31˚CDB
33˚CDB
14˚CWB
16˚CWB
18˚CWB
19˚CWB
20˚CWB
22˚CWB
24˚CWB
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
Hi
9.0
(m
3
/min)
10
2.87 2.46 3.01 2.42 3.12 2.54 3.17 2.51 3.23 2.48 3.32 2.58 3.41 2.51
12
2.82 2.44 2.96 2.40 3.07 2.52 3.13 2.49 3.19 2.46 3.28 2.56 3.38 2.50
14
2.77 2.41 2.90 2.38 3.03 2.50 3.09 2.47 3.14 2.45 3.25 2.55 3.34 2.49
16
2.71 2.39 2.85 2.35 2.98 2.48 3.04 2.46 3.10 2.43 3.21 2.54 3.31 2.48
18
2.66 2.36 2.80 2.33 2.93 2.46 3.00 2.43 3.05 2.41 3.17 2.52 3.27 2.46
20
2.60 2.33 2.74 2.30 2.88 2.44 2.95 2.42 3.01 2.39 3.13 2.51 3.23 2.45
22
2.54 2.30 2.68 2.27 2.83 2.42 2.90 2.40 2.96 2.37 3.08 2.49 3.19 2.44
24
2.48 2.27 2.62 2.25 2.78 2.40 2.85 2.38 2.91 2.36 3.04 2.48 3.15 2.43
26
2.42 2.25 2.56 2.22 2.72 2.37 2.80 2.36 2.86 2.34 2.99 2.46 3.10 2.41
28
2.35 2.22 2.49 2.20 2.67 2.35 2.75 2.34 2.81 2.32 2.95 2.45 3.06 2.40
30
2.29 2.17 2.43 2.17 2.61 2.33 2.69 2.32 2.75 2.30 2.90 2.43 3.01 2.39
32
2.22 2.10 2.36 2.14 2.55 2.31 2.64 2.30 2.70 2.28 2.85 2.42 2.96 2.36
34
2.15 2.04 2.29 2.11 2.49 2.28 2.58 2.28 2.64 2.26 2.79 2.39 2.91 2.35
35
2.12 2.01 2.26 2.10 2.46 2.27 2.55 2.27 2.61 2.25 2.77 2.39 2.89 2.34
36
2.08 1.97 2.22 2.08 2.43 2.25 2.52 2.25 2.58 2.24 2.74 2.38 2.86 2.33
38
2.01 1.91 2.15 2.04 2.36 2.23 2.46 2.23 2.52 2.21 2.69 2.36 2.81 2.32
39
1.97 1.87 2.11 2.00 2.33 2.21 2.43 2.22 2.49 2.20 2.66 2.35 2.78 2.31
Air flow
Outdoor
air temp.
Indoor air temp
21˚CDB
23˚CDB
26˚CDB
27˚CDB
28˚CDB
31˚CDB
33˚CDB
14˚CWB
16˚CWB
18˚CWB
19˚CWB
20˚CWB
22˚CWB
24˚CWB
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
Hi
9.5
(m
3
/min)
10
4.06 3.08 4.25 3.02 4.40 3.12 4.48 3.08 4.55 3.04 4.69 3.11 4.81 3.01
12
3.98 3.04 4.17 2.99 4.34 3.09 4.42 3.05 4.50 3.01 4.64 3.09 4.77 3.00
14
3.91 3.00 4.10 2.95 4.28 3.06 4.36 3.02 4.44 2.98 4.58 3.07 4.72 2.98
16
3.83 2.96 4.02 2.92 4.21 3.03 4.29 2.99 4.38 2.95 4.53 3.05 4.67 2.96
18
3.75 2.92 3.95 2.88 4.14 3.00 4.23 2.96 4.31 2.93 4.47 3.03 4.61 2.94
20
3.67 2.88 3.87 2.84 4.07 2.97 4.16 2.94 4.25 2.90 4.41 3.01 4.56 2.91
22
3.59 2.83 3.78 2.80 4.00 2.93 4.10 2.91 4.18 2.88 4.35 2.98 4.50 2.89
24
3.50 2.79 3.70 2.76 3.92 2.90 4.02 2.88 4.11 2.85 4.29 2.95 4.44 2.87
26
3.41 2.75 3.61 2.72 3.84 2.87 3.95 2.85 4.04 2.82 4.23 2.92 4.38 2.85
28
3.32 2.70 3.52 2.68 3.76 2.83 3.88 2.82 3.96 2.79 4.16 2.90 4.32 2.83
30
3.23 2.65 3.43 2.63 3.68 2.80 3.80 2.79 3.89 2.76 4.09 2.88 4.25 2.81
32
3.14 2.61 3.33 2.59 3.60 2.76 3.72 2.75 3.81 2.73 4.02 2.85 4.18 2.79
34
3.04 2.56 3.23 2.54 3.51 2.73 3.64 2.72 3.73 2.70 3.94 2.83 4.11 2.77
35
2.99 2.54 3.18 2.52 3.47 2.70 3.60 2.71 3.68 2.68 3.91 2.81 4.07 2.75
36
2.94 2.52 3.13 2.50 3.42 2.69 3.56 2.68 3.64 2.66 3.87 2.80 4.04 2.74
38
2.84 2.46 3.03 2.46 3.33 2.65 3.47 2.65 3.56 2.63 3.79 2.77 3.96 2.72
39
2.79 2.44 2.98 2.43 3.29 2.63 3.43 2.63 3.51 2.61 3.75 2.76 3.92 2.70
Note(1) These data show average statuses.
Depending on the system control, there may be ranges where the operation is
not conducted continuously.
These data show the case where the operation frequency of a compressor is
fixed.
(2) Capacities are based on the following conditions.
Corresponding refrigerant piping length :7m
Level difference of Zero.
(3) Symbols are as follows.
TC : Total cooling capacity (kW)
SHC : Sensible heat capacity (kW)
HC : Heating capacity (kW)
(2) 4way ceiling cassette type (FDTC)
Heating Mode (HC)
(kW)
(kW)
Heating Mode (HC)
(kW)
(kW)